EM-6489-B Rev.9 P. 10 / 47
CC-Link - OPERATIONS
CC-Link registers are assigned to program and operate the unit via CC-Link network. It can also disable the view switching
control via the front buttons to fix the display view to a specific parameter combination.
■
CC-Link REGISTER ACCESS SETTING
RGTR.
PARAMETER
4943
Deactivate CC-Link register writing protection
Writing a preset passcode in this register deactivates the writing protection via CC-Link.
When the CC-Link passcode set in this register matches the preset one, setting ‘1’ or ‘2’ in the register address 4945
becomes available to enable writing in CC-Link registers.
Reading out the register value is not possible. It reads always ‘-1’ regardless of the code setting.
After writing is complete, be sure to set a value other than the passcode (‘0’ is recommended) to activate the writing
protection again.
4945
CC-Link register access setting
0 : Write disable (*)
1 : Write enable
2 : Write enable the count values
Other : Write disable
This setting is erased when the power supply to the unit is removed. It always starts with ‘0’ (Write disable) when the
power supply is turned on. Set ‘1’ or ‘2’ before starting writing at other registers.
In order to write a count value (e.g. active energy), set ‘2’ at this register. When it is set, the unit stops counting so that
a new count value can be written in the register. Be careful to use ‘2’ setting because no counting will be performed if
the unit remains with this setting.
When the CC-Link register writing protection is enabled, this register setting cannot be changed from ‘0’ to ‘1’ or ‘2’ un-
less a correct security code is set in the register 4943.
(*) Factory setting
■
USER OPERATIONS
User operations include switching the display views and resetting alarm trips.
RGTR.
PARAMETER
5201
Button operation lock
0 : All key operations available (*)
1 : All key operations locked
2 : Lock the key operation to go to Setting mode only
5202
Data reading display
Shows the parameter set displayed on the three data displays. The display can be switched by writing at this address
from the host.
5203
Energy reading display
Shows the parameter type displayed on the bottom data display. The display can be switched by writing at this address
from the host.
5204
Energy reading display unit
0 : 0.1 kWh, 0.1 kvarh, 0.1 kVAh (*)
1 : 0.1 Wh, 0.1 varh, 0.1 VAh
Shows the unit (factor) of the parameter on the energy display (k = kilo). The display unit can be switched by writing
at this address from the host.
Exception: Count time (unit: h) is displayed always ‘without kilo’.
5205
Reset alarm trip
1 : Reset
0 : No resetting
5206
Automatic ∑ view switching
0 : Disable automatic switching (*)
1 : Enable automatic switching: ∑1 through ∑6 switched in 10 second intervals. Automatic switching is cancelled when
one of the front control buttons are touched.
(*) Factory setting