 LL (or L, H, HH, 1, 2) ALARM ON TIME DELAY

1)  Hold  down  [M]  for  3  seconds*  and  push  [M]  to  choose 

[LL].

2)  Press [UP] and [DOWN] buttons at once.  Current set

-

ting value in seconds is shown at the right end of the 
digital indicator, with ‘d.’ at the left end.

3)  Press [UP] or [DOWN] buttons until the meter shows the 

desired value, and press [SET].

  (Same procedure for L, H, HH, 1, 2 setpoints)

 MOVING AVERAGE SAMPLE NUMBER

1)  Hold  down  [M]  for  3  seconds*  and  push  [M]  to  choose 

[P].

2)  Press [UP] and [DOWN] buttons at once.  Current set

-

ting value is shown at the right end of the digital indica-

tor, with ‘A.’ at the left end.

3)  Press [UP] or [DOWN] buttons until the indicator shows 

the desired value (1, 2, 4, 8 or 16), and press [SET].

 LED BRIGHTNESS ADJUSTMENT

1)  Hold  down  [M]  for  3  seconds*  and  push  [M]  to  choose 

[P].

2)  Press [UP] and [DOWN] buttons at once for two times.  

Current setting value is shown on the digital indicator, 

with ‘c.’ at the left end.  Factory default setting is ‘7,’ the 

brightest.

3)  Press [UP] or [DOWN] buttons until the indicator shows 

the desired setting (1 through 7), and press [SET].

 RESET TO FACTORY SETTING

1)  Hold down [M] for 3 seconds* and press [M] to choose 

[P].

2)  Press [UP] and [DOWN] buttons at once for three times.

  ‘RSET’ starts blinking on the digital indicator.

3)  Press [SET] and [DOWN] buttons at once.

*The [M] button remain activated for 1 minute after it has 
been used to choose a indicator LED (programming mode).  
During this period, pressing the [M] button briefly is enough 
to choose another indicator.  After 1 minute, it turns to de

-

activated state.

CALIBRATION PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.

The reading can be finely adjusted to match it to a receiving 

instrument, or to compensate input wire resistance when 

the unit is combined with a zenor barrier.  Follow the regu

-

lar calibration procedure explained below:

 HOW TO CALIBRATE THE OUTPUT INDICATION

Use a signal source and measuring instruments of sufficient 

accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1)  ZERO:    Apply  0%  input  and  adjust  the  reading  to  0% 

following  the  procedure  explained  in  “ADJUSTMENT 
PROCEDURE.”

2)  SPAN:  Apply 100% input and adjust the reading to 100% 

following the same procedure.

3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce

-

dure 1) – 3).

MAINTENANCE

Regular checking procedure is explained below:

 CHECKING

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the reading 

for the respective input signal remains within accuracy de-
scribed in the data sheet.  When the reading is out of toler-

ance, recalibrate the unit according to the “CALIBRATION 
PROCEDURE” explained earlier.

Summary of Contents for 48NDR

Page 1: ...invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below AC rating 85 264V 50 60 Hz approx 5 5 8VA DC rating 24V 15 approx 3 5W ENVIRONMENT Indoor use If the unit s environmental protection is compromised e g when multiple units are to be mounted side by side when heavy dust or metal ...

Page 2: ...ction 138 1 0 L Panel thickness 1 6 8 0 mm L 31 5 36 N 1 N number of units 1 0 CLUSTERED MOUNTING no ingress protection 1 0 USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s...

Page 3: ...ze 31 5 138 mm Panel Watertight Packing 2 Push the mounting brackets into the grooves on top and bottom of the rear module until they hit the panel s rear side Leave at least 3 centimeters both above and below the unit for ventilation EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 ...

Page 4: ...xisting panel cutout of Fuji Electric PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 12 13 14 15 16 U V La Lb Lc 12 13 14 15 16 U V LLa 11 La LLb Lc LLc LOAD Inductive Load Coil Varistor or CR Circuit DC Powered LOAD Inductive Load Coil Diode Varistor or CR Cir...

Page 5: ...de 1 orange orange green orange Input L L Input H H Input green red H L Pattern 2 model suffix code 2 orange green green red red red H L 50 40 30 20 10 0 10 20 30 40 50 C C 100 SET H S P Z L 90 80 70 60 50 40 30 20 10 0 SET ENTER Button H Setpoint Adj Trip Indicator red Span Adj amber Decimal Point Position Adj amber Zero Adj amber L Setpoint Adj Trip Indicator green UP Button Mode Selector DOWN B...

Page 6: ... Delay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints...

Page 7: ...ue and press SET DIGITAL INDICATOR ZERO ADJUSTMENT 1 Apply 0 input signal 2 Hold down M for 3 seconds and push M to choose Z 3 Press UP or DOWN buttons until the digital indicator comes to a desired value and press SET BARGRAPH DIGITAL INDICATOR SPAN ADJUSTMENT 1 Apply 100 input signal 2 Hold down M for 3 seconds and push M to choose S 3 Press UP and DOWN buttons at once Blinking S LED is switched...

Page 8: ...ing on the digital indicator 3 Press SET and DOWN buttons at once The M button remain activated for 1 minute after it has been used to choose a indicator LED programming mode During this period pressing the M button briefly is enough to choose another indicator After 1 minute it turns to de activated state CALIBRATION PROCEDURE This unit is calibrated at the factory to meet the ordered specificati...

Reviews: