48NDR

P. 6 / 8

EM-9443 Rev.5

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

ADJUSTMENT PROCEDURE

L

SET

L

M

Increase / Decrease

L Setpoint

Complete

LL

SET

LL

M

Increase / Decrease

LL Setpoint

Complete

H

M

Press at once

ON Time Delay for 

H Setpoint

Increase / Decrease

Complete

Digital Indicator

H

SET

H

M

Increase / Decrease

H Setpoint

Complete

HH

SET

HH

M

Increase / Decrease

HH Setpont

Complete

2

SET

2

M

Increase / Decrease

Increase / Decrease

Setpoint 2

Complete

1

SET

1

M

Setpoint 1

Complete

LED OFF

LED OFF

LED Blinking

Mode Selector

*

1

UP / DOWN Button

UP / DOWN Button

LED Blinking

Mode Selector

*

1

UP / DOWN Button

LED Blinking

Mode Selector

*

1

UP / DOWN Button

LED Blinking

Mode Selector

*

1

 

ZERO ADJUSTMENT

: Apply 0% input signal before adjustment.  All alarm setpoints will be reset after the adjustment.

SET

H

HH

M

Press at once

ON Time Delay for 

HH Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

HH

 L

M

Press at once

ON Time Delay for 

L Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

L

LL

M

Press at once

ON Time Delay for

LL Setpoint

Increase / Decrease

Complete

Digital Indicator

SET

LL

Z

M

Press at once

Zero Adjustment

Digital Indicator / Bargraph

Z

SET

Z

M

Increase / Decrease

Zero Adjustment

Digital Indicator Only

Complete

Z

ON

LED OFF

 

SPAN ADJUSTMENT

: Apply 100% input signal before adjustment.  All alarm setpoints will be reset after the adjustment.

S

LED OFF

 

DECIMAL POINT POSITION

 

ALARM SETTING

: Proceed after the zero / span adjustments and the decimal point position setting.

• 48NDR-4, 48NDR-2

 

*

2

• 48NDR-0

 

*

3

*

1. Keep pressing at least for 3 seconds to activate Mode Selector M.  Press briefly for second and more times within 1 minute after it has been activated.

*

2. HH or LL setpoints are not provided for the 48NDR-2.

*

3. 1 or 2 setpoints are not provided for the 48NDR-0R, -0Y, -0G or -0B.

Each setting sequence is complete only when SET button is pressed.  Once set, parameters are not lost even after the power is removed.

M

Press at once

Span Adjustment

Digital Indicator / Bargraph

S

SET

S

M

Increase / Decrease

Span Adjustment

Digital Indicator Only

Complete

S

ON

P

SET

M

Increase / Decrease

Decimal Point Position

Complete

P

Summary of Contents for 48NDR

Page 1: ...invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below AC rating 85 264V 50 60 Hz approx 5 5 8VA DC rating 24V 15 approx 3 5W ENVIRONMENT Indoor use If the unit s environmental protection is compromised e g when multiple units are to be mounted side by side when heavy dust or metal ...

Page 2: ...ction 138 1 0 L Panel thickness 1 6 8 0 mm L 31 5 36 N 1 N number of units 1 0 CLUSTERED MOUNTING no ingress protection 1 0 USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s...

Page 3: ...ze 31 5 138 mm Panel Watertight Packing 2 Push the mounting brackets into the grooves on top and bottom of the rear module until they hit the panel s rear side Leave at least 3 centimeters both above and below the unit for ventilation EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 ...

Page 4: ...xisting panel cutout of Fuji Electric PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 12 13 14 15 16 U V La Lb Lc 12 13 14 15 16 U V LLa 11 La LLb Lc LLc LOAD Inductive Load Coil Varistor or CR Circuit DC Powered LOAD Inductive Load Coil Diode Varistor or CR Cir...

Page 5: ...de 1 orange orange green orange Input L L Input H H Input green red H L Pattern 2 model suffix code 2 orange green green red red red H L 50 40 30 20 10 0 10 20 30 40 50 C C 100 SET H S P Z L 90 80 70 60 50 40 30 20 10 0 SET ENTER Button H Setpoint Adj Trip Indicator red Span Adj amber Decimal Point Position Adj amber Zero Adj amber L Setpoint Adj Trip Indicator green UP Button Mode Selector DOWN B...

Page 6: ... Delay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints...

Page 7: ...ue and press SET DIGITAL INDICATOR ZERO ADJUSTMENT 1 Apply 0 input signal 2 Hold down M for 3 seconds and push M to choose Z 3 Press UP or DOWN buttons until the digital indicator comes to a desired value and press SET BARGRAPH DIGITAL INDICATOR SPAN ADJUSTMENT 1 Apply 100 input signal 2 Hold down M for 3 seconds and push M to choose S 3 Press UP and DOWN buttons at once Blinking S LED is switched...

Page 8: ...ing on the digital indicator 3 Press SET and DOWN buttons at once The M button remain activated for 1 minute after it has been used to choose a indicator LED programming mode During this period pressing the M button briefly is enough to choose another indicator After 1 minute it turns to de activated state CALIBRATION PROCEDURE This unit is calibrated at the factory to meet the ordered specificati...

Reviews: