background image

MODEL: 47LV

http://www.m-system.co.jp/

47LV SPECIFICATIONS

ES-9502 Rev.12   Page 2/7

steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to DC output to HH output or H output to
 L output or LL output to power
Setting: (Front button)
• Scaled range
• Input type
• Alarm setpoint
• Hysteresis (deadband)
• Moving average
• Others
(Refer to the instruction manual for details)
Read rate: 40 times/sec. (25 msec.)
Averaging: None or moving average
Lockout setting: Prohibiting certain operations; protecting
settings

DISPLAY

Display: 16 mm (.63) high, 4 ½ digits, 7-segment LED
Display range: -19999 to 19999
Decimal point position: 10

–1

, 10

–2

, 10

–3

, 10

–4

 or none

Zero indication: Higher-digit zeros are suppressed.
Over-range indication: ‘-19999’ or ‘19999’ blinking for
display values out of the display range.
‘S.ERR’ and ‘Min’ or ‘Max’ blinking when the input signal is
out of the usable range.
Alarm status indication
  LL indicator: Green LED turns on when the LL alarm is
tripped.
  L indicator: Green LED turns on when the L alarm is
tripped.
  H indicator: Red LED turns on when the H alarm is tripped.
  HH indicator: Red LED turns on when the HH alarm is
tripped.
  P indicator: Amber LED turns on when none of the other
alarms is tripped.
Only ‘P’ turns on with no-alarm-output type. ‘LL’ or ‘HH’
does not turn on with dual-alarm-output type.
All setpoints can be independently set either for Hi or Lo
alarm trip.
Function indicators:
Zro, Spn, D/P, Tch, Fnc, Min, Max
Display mode status and operation status, amber ON or
blink
Engineering unit indication: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s

2

, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m

3

, m

3

/sec,

m

3

/min, m

3

/h, Nm

3

/h, N·m, N/m

2

, g, kg, kg/h,

N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.

INPUT SPECIFICATIONS

Default setting
Input code 1: Measuring range ±10 V
Input code 2: Measuring range ±1 V
Input code 3: Measuring range ±200 V
Input code 4: Measuring range ±100 μA
Input code 5: Measuring range ±2 A
Input code 6: Measuring range ±700 V
Overload capacity
Input code 5: ±3 A for 10 sec.,  ±2.4 A continuous
Input code 6: ±1000 V for 10 sec., ±840 V continuous

 DC INPUT

TYPE 

MEASURING  OPERATIONAL 

INPUT   

 

IND 

RANGE 

RANGE 

IMPEDANCE

  V10 

±10V 

-11 – +11V 

1MΩ minimum

 

V5 

±5V 

-5.5 – +5.5V 

1MΩ minimum

  V0-5 

0 – 5V 

-0.3 – +5.3V 

1MΩ minimum

  V1-5 

1 – 5V 

0.7 – 5.3V 

1MΩ minimum

  A0-2 

0 – 20mA 

-2 – +22mA 

approx. 10Ω

  A4-2 

4 – 20mA 

2 – 22mA 

approx. 10Ω

 

V1

-1.1 – +1.1V

  1MΩ minimum

  V01 

±100mV 

-110 – +110mV  1MΩ minimum

  V001 

±10mV 

-11 – +11mV 

1MΩ minimum

 

A1 

±1mA 

-1.1 – +1.1mA 

approx. 100Ω

  V200 

±200V 

-220 – +220V 

1MΩ minimum

  A100 

±100mA 

-110 – +110mA 

approx. 10Ω

±1V 

  A01            ±100μA        -110 – +110μA      approx. 1kΩ

  A2-2           ±2A               -2.2 – +2.2A         approx. 0.1Ω

  A1-1           ±1A               -1.1 – +1.1A         approx. 0.1Ω

 V700          ±700V           -770 – +770V      1MΩ minimum

OUTPUT SPECIFICATIONS

■ DC Output
• DC Current
Operational range: -5 – +105 %
• DC Voltage
Operational range: -5 – +105 %
■ Alarm Output: Relay contact
Rated load: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage: 250 V AC, 30 V DC
Maximum switching power: 750 VA, 90 W (resistive load)
Minimum load: 5 V DC @ 10 mA
Mechanical life: ≥ 5 × 10

6

 cycles (rate 180 cycles/min.)

INSTALLATION

Power consumption
•AC: Approx. 6.5VA
•DC: Approx. 3 W
Operating temperature: -10 to +55°C (14 to 131°F)

Summary of Contents for 47LV

Page 1: ...Load resistance 1000 min CE not available 4 0 10 V DC Load resistance 10 k min 5 0 5 V DC Load resistance 5000 min 6 1 5 V DC Load resistance 5000 min 4W 10 10 V DC Load resistance 10 k min 3 ALARM O...

Page 2: ...ber ON or blink Engineering unit indication Sticker label attached DC AC mV V kV A mA A kA mW W kW var kvar Mvar VA Hz k M cm mm m m sec mm min cm min m min m h m s 2 inch s min h m 3 m 3 sec m 3 min...

Page 3: ...0 V DC Dielectric strength 2000 V AC 1 minute input to DC output to HH output or H output to L output or LL output to power to ground STANDARDS APPROVALS EU conformity EMC Directive EMI EN 61000 6 4 E...

Page 4: ...Used to move on to the scaling and other setting modes or to shift through setting items in each through setting items in each setting mode 7 Shift button Used to move on to the setting standby status...

Page 5: ...MODEL 47LV http www m system co jp 47LV SPECIFICATIONS ES 9502 Rev 12 Page 5 7 MOUNTING REQUIREMENTS unit mm 92 0 8 0 45 0 6 0 min 120 min 75 Panel thickness 1 6 to 8 0 mm...

Page 6: ...play Setting 2 3 4 INPUT LL OUTPUT L OUTPUT H OUTPUT L OUTPUT H OUTPUT HH OUTPUT 1 5 6 9 10 POWER U V ALARM OUTPUT CODE 0 No alarm output A D Converter Digital Computation Display Setting 2 3 4 INPUT...

Page 7: ...PE MEASURING INPUT indicator RANGE TERMINALS V200 200V 1 4 V10 10V V5 5V V1 1V V01 100mV 2 4 V001 10mV INPUT TYPE MEASURING INPUT indicator RANGE TERMINALS V0 5 0 5V 2 4 V1 5 1 5V A100 100mA 3 4 A1 1m...

Reviews: