47LCT
P. 8 / 16
EM-9507-B Rev.6
...
...
...
...
...
...
PARAMETER
Input type
Input scaling value A
Display scaling value A
Input scaling value B
Display scaling value B
Decimal point position
4 positions or none
Decimal point position
Display value for Input Scaling Value B
Input value for Full-scale point:
Set to a specific value by using the
buttons, or by Teach Calibration
Display value for Input Scaling Value A
Input value for Zero point:
Set to a specific value by using the
buttons, or by Teach Calibration
Measuring range 0 to 5A
Measuring range 0 to 1A
INDICATORS
FUNCTION
DEFAULT
VALUE
DISPLAY
Zro
Spn
Zro
Tch
Zro
D/P
Spn Tch
Spn D/P
D/P
Analog output action
Proportional to the display value
Fnc
Zro
Spn Fnc
Proportional to the scaling value
Analog output 0%
adjustment
Analog output 0% adjustment:
adjustable range -5 to 105%
(increasing)
(decreasing)
(increasing)
(decreasing)
Fnc
Analog output 100%
adjustment
Analog output 100% adjustment:
adjustable range -5 to 105%
Scaling setting:
The 0% and 100% of the measurement range can be set to the desired values by setting parameters.
Note: After initialization, the parameters will return to the default values.
Input Scaling Value A
Enter the desired zero value (0%). (Input scaling value A < Input scaling value B)
Input Scaling Value B
Enter the desired full scaling value (100%).
Note: For setting input scaling value A and B, proceed with the same method. The combination of inputting parameter and Teach Calibra-
tion is unable.
For product version 1.04 or eariler;
Input Scaling Value A
"0.0" is displayed as factory default setting or after initialization. For setting desired input scaling value A, calculate by using the formula
shown below. (Input scaling value A < Input scaling value B)
(Example)
Input type: 0 to 5A
Input scaling: 4 to 5
4 + (5 x (5 / 100)) = 4.25
(Zero value) (5% value of full scale of input type 0 to 5A)
Input Scaling Value B
Enter the desired full scaling value (100%).
Decimal point position: Decimal point position is specified independently from the scaling. When you set the display scaling, include
zeros for fractions (10000 to show 10.000).
Analog output: When the forced zero or low-end cutout is ON, the analog output is proportional to the display value.
Analog output 0% / 100% adjustment: Pressing [Shift] button switches the signal to increase or decrease, and then pressing [Up] button
controls it toward the desired output value. 0% value < 100% value