47DAC OPERATING MANUAL EM-9518-B Rev.4
25. CONFIRMING AND CONFIGURING ALARM SETPOINTS
The alarm setpoints can be confirmed on the sub display while in Measuring Mode. Each time pressing Alarm/
↓
button
during Measuring Mode, the indication is switched in the order of LL alarm setpoint to L alarm setpoint to H alarm setpoint
to HH alarm setpoint and back to the original bank No. indication. The measured value is updated while in confirming the
setpoints.
These setpoints can be changed in this status without moving on to Alarm Setting Mode. If the front buttons are left
untouched for the specified time period while in confirming the setpoints, the sub display can be set to return to the bank
No. indication.
■
PROCEDURE TO CONFIRM ALARM SETPOINTS
Each time pressing Alarm/
↓
button in Measuring Mode, the sub display indication is changed from the bank No. to LL alarm
setpoint to L alarm setpoint to H alarm setpoint to HH alarm setpoint and back to the bank No.
NOTE
• When the bank switching is set to “disabled”, the bank No. is not indicated.
• The alarm setpoints cannot be confirmed when the alarm setting lockout is set to “lock Alarm Setting Mode”.
• Switching the banks is not available in this mode.
• The alarm setpoints can be confirmed while ‘S.ERR’ is indicated. However the SD indicates ‘OVER’ instead of the bank
No.
■
CONFIGURATION OF ALARM SETPOINTS
The alarm setpoints can be changed while in confirming in Measuring Mode without moving on to Alarm Setting Mode.
Refer to the following OPERATING PROCEDURE.
■
MANUAL SUB DISPLAY RESET
If the front buttons are left untouched for the specified time period while in confirming the alarm setpoints, the automatic
reset of the SD to the bank No. indication (‘OFF’) or manual reset (‘ON’) can be selected. The default setting is “alarm set-
point display automatically reset” (‘OFF’). The automatic return time is the same as the time set with the “automatic return
time to Measuring Mode”.
*
1 Display depends on the settings and input.
H alarm setpoint
HH alarm setpoint
‘H’ indicator blinking
‘HH’ indicator blinking
‘L’ indicator blinking
‘LL’ indicator
blinking
L alarm setpoint
LL alarm setpoint
Bank No.
Alarm/
↓
Alarm/
↓
Alarm/
↓
Alarm/
↓
Alarm/
↓