• Fine Output Calibration

Using the Programming Unit (ITEM 19, 20)

ITEM 19 is for Zero, and ITEM 20 is for Span.

1) Turn the unit into Program mode (ITEM 01).
2) Apply simulated 0% input.  Increase/decrease values 

(default: 0%) at ITEM 19 until the output signal is cali-

brated to actual 0%.

3) Apply simulated 100% input.  Increase/decrease value 

(default: 100%) at ITEM 20 until the output signal is cali-

brated to actual 100%.

4) Apply simulated 0% input again and check 0% output.
5) When 0% value is changed, repeat the above procedure 

2) – 4).

  The 0% value may be shifted when the output span is 

greater than the input span (gain > 1).

• Using Linearization Table

Please have the PU-2x Operation Manual ready at hand.   
Max. 16 calibration points defined by sets of input and out-
put values can be programmed.  Use only necessary number 
of points, arranged in order from the smallest input value.
Enable use of the linearization table (ITEM 10: Pm-2: 
curved) in order to activate the settings.
     

X (nn) : Input Signal in %

     

Y (nn) : Output Signal in %

     

X or Y : -15.00 to +115.00%

-15%

0

X01

X02

X03

X04

X05 +115%

Y01

Y02

Y03

Y04

+100%  Y05

INPUT

OUTPUT

-5%

Figure 3. Linearization Table

[GROUP 01]

ITEM

MDFY.

DATA EXAMPLE

60
61

P
P

X (01) : XXX.XX
Y (01) : XXX.XX

62
63

P
P

X (02) : XXX.XX
Y (02) : XXX.XX

64
65

P
P

X (03) : XXX.XX
Y (03) : XXX.XX

66
67

P
P

X (04) : XXX.XX
Y (04) : XXX.XX

68
69

P
P

X (05) : XXX.XX
Y (05) : XXX.XX

70
71

P
P

X (06) : XXX.XX
Y (06) : XXX.XX

72
73

P
P

X (07) : XXX.XX
Y (07) : XXX.XX

74
75

P
P

X (08) : XXX.XX
Y (08) : XXX.XX

76
77

P
P

X (09) : XXX.XX
Y (09) : XXX.XX

78
79

P
P

X (10) : XXX.XX
Y (10) : XXX.XX

80
81

P
P

X (11) : XXX.XX
Y (11) : XXX.XX

82
83

P
P

X (12) : XXX.XX
Y (12) : XXX.XX

84
85

P
P

X (13) : XXX.XX
Y (13) : XXX.XX

86
87

P
P

X (14) : XXX.XX
Y (14) : XXX.XX

88
89

P
P

X (15) : XXX.XX
Y (15) : XXX.XX

90
91

P
P

X (16) : XXX.XX
Y (16) : XXX.XX

Modification Code

S: Modifiable at any time.
P:  Modifiable only when the MAINTENANCE SWITCH is in 

the “PRG” mode.

Reviews: