background image

WIRING INSTRUCTIONS

 

M4 Screw (power input, power unit)

Torque: 0.8 N∙m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the power ter-

minals.

3) Installation & environment

MAINTENANCE

Model HDC4-x-R is available as spare part to replace the 
AC power unit. 
Power units’ standard life is expected for 10 years with 
average ambient temperature 35°C (95°F) and 1.0A load. 
Contact M-System for use in extremely different conditions.

 

HOW TO REPLACE THE POWER UNIT

1) Prepare Power Unit (switching regulator) model HDC4-

x-R.

2) Turn off the power supply connected to the Power Unit.
3) Remove the wire binding and wiring connected to the ter-

minal 1 – 2 and 4 – 5.

4) Loosen and remove the mounting screws 

A

 (2 places).

5) Detach the Power Unit from the Rack.
6) Attach the new Power Unit to the Rack and tighten the 

screws in reverse order as explained above.  The tighten-

ing torque of the mounting screws 

A

 is 0.8 N·m.

A  : Mounting screws
1  : 24V DC (+)
2  : 24V DC (–)
3  : FG
4  : AC power (V)
5  : AC power (U)

1 2 3 4 5

A

A

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

17BXE-U1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]