Liquid Cooling System LCS20 Series Technical Manual
Manual# 820-0166, Rev. J, 03/06/19
22
of
32
STARTUP PROCEDURE & SYSTEM OPERATION
1. Verify that the coolant reservoir is full.
2. Start facility water flow to the LCS.
3. Verify that the unit is plugged into the correct operating voltage and the circuit breaker located on the
rear panel is in the “on” position.
4. Check that the hose connections leading from the supply and return ports on the rear panel of the
unit to the device being cooled are securely in place.
5.
Turn the rocker switch located on the control panel to the “on” position. The controller will energize
and go through a diagnostic test. The pump will start.
x
Press the “set” button on the controller once to display the current coolant temperature set
point.
x
Press the “up” and “down” arrow key to get to the desired coolant temperature set point.
Press “set” key to accept the set point and ret
urn to normal operation.
6. Operate the LCS for 2-3 minutes then check the coolant level. The coolant level should drop as a
result of the water line filling up. Add water to bring coolant level up to top of tank.
7. Inspect all fittings and hoses for leaking. If a leak is detected, turn off LCS, disconnect power, and
repair the leak.
Summary of Contents for LCS20 Series
Page 14: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 14 of 32...
Page 15: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 15 of 32...
Page 16: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 16 of 32...
Page 17: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 17 of 32...
Page 18: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 18 of 32...
Page 19: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 19 of 32...