Selecting LCS Location
To minimize the heat gain and pressure drop through the connecting hoses, the LCS should be
located as close as possible to the heat load (user equipment). This is more important for units with
centrifugal pumps. Coolant lines are best run at or near the same level as the cooling system. Once
the chiller is in position lock the casters.
The top clearance must be at least 6" for remov
al of the cover and at least 6” around four sides for
removal of side panels and access of internal components.
Before moving the LCS cap all ports to prevent any coolant leakage. Unlock the casters and move
to new location. Once in the new location lock the casters.
Storing LCS
Do not operate or store chillers outside. These systems are not intended or outdoor
use.
To prevent freezing during storage drain water if the chiller is located in an area below
10
q
C (50
q
F).
If unit is to be out of use for more than 1 week, drain all liquid from chiller to prevent algae growth.
Summary of Contents for LCS20 Series
Page 14: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 14 of 32...
Page 15: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 15 of 32...
Page 16: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 16 of 32...
Page 17: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 17 of 32...
Page 18: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 18 of 32...
Page 19: ...Liquid Cooling System LCS20 Series Technical Manual Manual 820 0166 Rev J 03 06 19 19 of 32...