background image

GUIDELINE FOR FIELD INSTALLATION

The 

LED-BP-SLIM-XX Series ELBP-XX-S units

 is suitable for field installation with suitable LED 

loads including LED luminaires, LED lamps and others. Follow below 3 steps to determine if 
your luminaire is eligible for field installation.  

1) Determine Electrical Compatibility

     Verify that the

 emergency driver selected does not exceed the power delivered to the LED 

     loads (both voltage and current) of the normal LED driver.

2) Calculate Lumen Output in

 

Emergency Mode

A) Access luminaire data from

 Design

lights Consortium website

 (www.designlights.org).

B) 

Select “Search the DLC Qualified Product List’ on the DLC homepage.

C) 

Enter luminaire

 manufacturer name and 

part

 

number

 in the “search by keyword” text 

     

window.

D) 

Select ”Search” tab to open the “Qualified Products List”.

E) 

Determine luminaire Lumens per Watt efficacy in “Rated Data” specifications.

F) 

Multiply luminaire Lumens per Watt by Emergency rated output of the 

ELBP-XX-S

 

series

 

     (

Refer

 

to

 

the table below

).

3) Determine Suitability of Means of Egress Lighting Levels

Using industry standard lighting design software with the

 IES files 

for

 

the

 

emergency

 

luminaires

, verify that the 

above

 

calculated

 

emergency

 

lumens are sufficient to meet 

Code-compliant path of egress illumination levels.

While the LED-BP-SLIM-XX Series, ELBP-XX-S

 

equipment

 has been found compliant with 

the requirements of UL Standard 924, 

it is ultimately the responsibility of the Designer/

Specifier to assure the as

-installed system 

delivers code-compliant path of egress 

illumination in accordance with national

state and

 

local code

 requirements.

LED-BP-SLIM-XX SERIES, ELBP-XX-S SPECIFICATIONS

6/6

        MODEL / CATALOG NUMBER

EMERGENCY

 

OUTPUT

(

CONSTANT

)

 

9 WATTS

13.5 WATTS

LED-BP-SLIM-9W-TB / ELBP-9W-S-TB

LED-BP-SLIM-13.5W-TB / ELBP-13.5W-S-TB

            1-800-982-4587
www.lvscontrols.com

Summary of Contents for LED-BP-SLIM Series

Page 1: ...tlets or other hazardous location 8 Use this product in 0 C minimum 55 C maximum ambient temperatures Ta 9 Do not attempt to service the batteries A sealed non maintenance battery is used that is not field replaceable Contact the manufacturer for information or service 10 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition and void warranty 11 Do not use...

Page 2: ...fter installation Drill a 1 2 12 mm hole for mounting the LTS Connect the wires from LTS to the LED BP SLIM model according to the wiring diagram on page 3 INSIDE THE LUMINAIRE LED test switch LED BP SLIM XX TB LED BP SLIM MODEL SPECIFICATIONS MODEL EMERGENCY OUTPUT CONSTANT 4 5 WATTS 13 5 WATTS LED BP SLIM 4 5W LED BP SLIM 4 5W TB VOLTAGE OUTPUT 5 200 VDC 15 300 VDC LED BP SLIM 9W LED BP SLIM 9W ...

Page 3: ...LUMINAIRE FOR DC LED LOAD N L L IN L OUT LED Test Switch Red White LED DRIVER N L Red White LED Test Switch LED LOAD LED LED Red Blue Blue White Red Blue White Input Output Output Gray White Black Green Yellow Switch Black White Black HOT Common GND LINEAR EMERGENCY EQUIPMENT Green Yellow N L L IN L OUT LED Test Switch Red White LED Test Switch N L Red Blue Blue White Red Blue White AC LED TUBE BU...

Page 4: ...es out 1 800 982 4587 www lvscontrols com LED BP SLIM 4 5W TB LED BP SLIM 9W TB Item No L1 mm inch 200 7 87 W mm inch H mm inch 260 10 24 345 13 58 410 16 14 190 7 48 250 9 84 335 13 19 400 15 70 30 1 18 22 0 87 30 1 18 22 0 87 30 1 18 22 0 87 30 1 18 22 0 87 M Mounting mm inch LED BP SLIM 13 5W TB LED BP SLIM 18W TB Dimension unit mm inch LED BP SLIM 4 5W LED BP SLIM 9W Item No L1 mm inch 258 10 ...

Page 5: ...ys after initial power on Then monthly tests will be performed every 30 days b Annual Auto test will occur every 52 weeks after initial power on Monthly Auto Test The Monthly Auto Test shall be executed every 30 days and will test Normal to emergency transfer function emergency charging and discharging conditions are normal Monthly test time is approximately 30 60 seconds Annual Auto Test Annual A...

Page 6: ...uminaire Lumens per Watt efficacy in Rated Data specifications F Multiply luminaire Lumens per Watt by Emergency rated output of the ELBP XX S series Refer to the table below 3 Determine Suitability of Means of Egress Lighting Levels Using industry standard lighting design software with the IES files for the emergency luminaires verify that the above calculated emergency lumens are sufficient to meet ...

Reviews: