CB1224xA: Smart Battery Charger

 

Thank you for having chosen one of our products for your work.  
We are certain that it will give the utmost satisfaction and be a notable help on the job. 

 
 

General Description  

The CB series is a “Switching technology” and “Battery Care philosophy” since many years parts of 
the know-how ADEL system, led to the development of this advanced multi-stage battery charging , 
completely automatic and suited to meet the most advanced requirements of battery manufacturers. 
The  Battery  Care  concept  is  based  on  algorithms  that  implement  rapid  and  automatic  cycle  of 
battery  charging,  battery  charge  optimization  during  time,  flat  batteries  recovery  and  real  time 
diagnostic  during  installation  and  operation.  The  Real  Time  Auto-diagnostic  system,  monitoring 
battery faults such as, elements in short circuit, accidental reverse polarity connection, disconnection 
of  the  battery,  they  can  easily  be  detected  and  removed  by  help  of  Blink  Code  of  Diagnosis  Led; 
during the installation and after sell. Each device is suited for all battery types, jumper selection sets 
a predefined curves for: Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd and Ni-Mh. A rugged casing 
with bracket for DIN rail mounting provide IP20 protection degree. 

 
Main Characteristic 

 

Input: Single-phase  

115 – 230 – 277 Vac 

 

Output Battery: charging: 24 Vdc 5 A; 12 Vdc 6 A 

 

Suited for  the following battery types:  Open Lead  Acid,  Sealed 
Lead Acid, lead Gel and Ni-Cd Ni-Mh. 

 

Automatic  diagnostic  of  battery  status.  Charging  curve  IUoUo, 
constant voltage and constant current Battery Life Test function 
(Battery Care) 

 

Switching technology 

 

Three charging levels: Boost, Trickle and Recovery 

 

Protected against short circuit, Over Load and inverted polarity  

 

Signal output (contact free) for discharged or damaged battery  

 

Protection degree IP20 - DIN rail; Space saving 

 
 
Safety and warning notes 

WARNING 

–  Explosion  Hazard  Do  not  disconnect  Equipment  unless  power  has  been  switched  off  or  the  area  is 

known to be non-hazardous.  

WARNING 

– Explosion Hazard. Substitution of components may impair suitability for class I, Division 2. 

WARNING

 – Switch off the system before connecting the module. Never work on the machine when it is 

live.  The  device  must  be  installed  in  according  with  UL508.  The  device  must  have  a  suitable  isolating 
facility outside the power supply unit, via which can be switched to idle. Danger of fatal Injury! 

Connection (terminal and wiring): 

Cable Connection: 

The following cable cross-sections may be used: 

 

Solid 

(mm

2

Stranded 

(mm

2

AWG 

Torque (Nm) 

Stripping 

Length 

1 Phase L N PE 

Input AC 

1 Phase L N PE 

Input AC 

In:

0.2 – 2.5 

0.2 – 2.5 

24 – 14 

0.5 – 0.6 Nm 

7 mm 

 

 

Out:

0.2 – 2.5 

0.2 – 2.5 

24 – 14 

0.5 – 0.6 Nm 

7 mm 

Signal:

0.2 – 2.5 

0.2 – 2.5 

24 – 14 

0.5 – 0.6 Nm 

7 mm 

 
Use only copper cables that are designed for operating temperatures of > 75 °C. Wiring terminal shall be marked to 
indicate the proper connection for the power supply. 

 

P

ag

3

 

C

h

a

p

te

r

O

p

e

ra

ti

n

g

 a

n

d

 D

is

p

la

y

 E

le

m

e

n

t:

 

 

 
 

No. 3: Signal Ports (output Isolated): 

Connections for Fault Alarm Relay: Low Battery, Fault connections systems, Battery replacement. Contact: 3,4,5 

Relay Contact Rating:  

Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A : Resistive load (EN 60947-4-1) 

Min.1mA at 5 Vdc: Min. permissive load 

 

Signal Output port true table:

 

Led N°8 Battery Fault 

 

 

3-4 Closed 

3-5 Closed 

Battery or system Fault? 

YES 

 

 - led On 

NO 

 - led off 

 

Please see the NOTE at the bottom of this page. 
 

No. 4: Battery Connection Port: 

Connect the battery between pin. 1 (+) and 2 (–). 
One battery (12 Vdc) for 12 Vdc Output;  
Two battery (12 Vdc) for 24 Vdc Output;  

No. 5: Output Voltage Configuration 

This setting must be do with mains off. This jumper set the voltage of the batteries connected at the CB, is most 
important to check the correct voltage value on the batteries. If is connected a wrong battery the device show the 
fault indication of 1 blink. 

No. 6: Enable Power Supply  

This function allow at the Battery Charger to work like a Power Supply. To enable this function the operator must insert 
a jumper in Pos. 6 Enable Power Supply with the CB unpowered. 

When the device is turned ON we will have voltage 

to the output terminals OUTPUT BATTERY even if the battery is not present. After about 10 sec. without detecting a 
battery  the  CB  signals  with  2  blink  Battery  Not  connected  and  switches  the  alarm  relay.

 

If  the  battery  was  already 

present at power on or if it is connected at a later time, the CB detects the battery and starts to charge, if there is no 
fault deactivates the alarm relay and the LED DIAGNOSIS indicates the charging status. In Back Up (no Mains) and 
cell voltage < 2.18V (Pb batteries) or < 1.37V (NiCd batteries) for more than 30 sec. the system turns off completely

 

No. 7 and 8 Display Signals 

No.8:  Led Battery Fault connections systems, Battery Fault. 
No.7:  Led Diagnosis,  
   

Led Diagnosis. Diagnosis of the system through “blinking code” signal  

 

Monitoring 

Control 

Chart: 

State 

LED Diagnosis 
(No.7) 

LED Battery 
Fault (No.8) 

Charging 

Type 

 

Trickle 

1 Blink/ 2 sec 

OFF 

Absorption 

1 Blink/sec 

OFF 

Boost 

2 Blink/sec 

OFF 

Recovery (*) 

5 Blink/sec 

OFF 

Auto 

diagnosis of 

the system 

 

Reverse polarity or wrong battery voltage (for example: 
CB set for 24Vdc and battery 12Vdc) 

1 Blink/pause 

 

ON 

Battery Not connected 

2 Blink/pause 

 

ON 

Element in Short Circuit 

3 Blink/pause 

 

ON 

Over Load or Short Circuit on the load (with Enable Power 
Supply) 

4 Blink/pause 

 

ON 

Alarm Low Battery Voltage:  12Vdc, range 8-10 Vdc  
 

ONLY on REQUEST

 

24Vdc, range 18-21 Vdc  

9 Blink/pause 

 

ON 

Alarm High Battery Voltage: 12Vdc, over 14 Vdc  
 

ONLY on REQUEST

 

24Vdc, over 28 Vdc  

10 Blink/pause 

  ON 

 

 

 

 

 

 

 

NOTE: (*) In 

Recovery

 the LED Battery Fault (No.8) is OFF but the Relay is in failure mode (3-5 Closed) to indicate a 

battery with very low voltage.

 

Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy 

 

 

Tel. +39 0522 345518 – Fax +39 0522 345551 – mail: [email protected] 

www.adelsystem.com 

 

Instruction Manual CB12245A r8.doc 

 

P

ag

C

h

ap

te

r:

 

 

O

u

tp

u

P

o

w

e

c

o

n

n

e

c

ti

o

n

s

:

  

Output Power connections: 

 

Normal connection  

Typical application: 

-  One battery (12Vdc) for 12 Vdc Output. 

Set No Jumper in Pos. 5  

-  Two battery (12Vdc) for 24 Vdc Output  

Set Jumper in Pos. 5 

(See the table below at the point No. 2.) 
 
 

Operating and Display Element:  

 
 

No. 1: Input AC Port pin. L – N: 

1 Phase Switching Power Supplies L, N, PE  . 
 

No. 2: Battery Management Configurations 

Preliminary Operations: One device for all battery types. 
Completely  automatic,  all  devices  are  suitable  to  charge  most 
batteries types thank to User Selectable charging curves. They 
can charge open lead acid, sealed lead acid, Gel and Ni-Cd, Ni-Mh 
batteries.  It  is  possible  to  change  or  add  other  charging  curves 
connecting the device to a portable PC. 
Caution: Switch off the system before setting the jumper.  
 
 

Battery Type 

Selection 

Jumper Position 

 

Trickle/Float charge 

(Volt/Cell) 

Fast/Bulk charge 

(Volt/Cell) 

Open Lead 

 

2.23 

2.40 

Sealed Lead Low 

 

2.25 

2.40 

Gel Battery

 

 

2.30 

2.40 

NiCd – NiMh (Note 1)

 

 

1.40 – (12V) 10cells 

  1.40 – (24V) 20cells 

1.50 – (12V) 10cells 

  1.50 – (24V) 20cells 

 

Functional Setting 

 

Function 

Jumper Fast  

Charge Enable   

(Note 2) 

 

Jumper present: 
Fast charge enabled.  
Not used in Ni-Cd option 

Output Voltage 

Configuration 

(Pos. 5) 

 

Jumper Not Present:  

12 V Output 

Jumper present:  

24 V Output 

Power Supply 

Function  

(Pos. 6)  

 

Jumper Present: 
Power supply function enabled. 

 
Note:  

NiCd-NiMh: End-of-charge detected by a “flat” profile. If flat profile is detected, fast charge is terminated after 10 
min. General end-of-charge timeout set to 8 hours.  
 

This function is a hot swap (is possible to enable or disable with mains on). 

 

 
 

 

 

P

ag

4

 

C

h

a

p

te

r

B

a

tt

e

ry

 C

a

re

 

 

 

No. 9: Charging Level Current: 

 
 
It  is  possible  set  the  max  recharging  current  for  the  batteries  by  trimmer  (Charging 
Level).  The  current  adjustment  goes  from  10%  ÷  100%  of  In.  Set  the  maximum 
charging current between 10% and 20% of the battery capacity. 
 
 

 

Charging Curve 

Automatic multi-stage  operation  and  real time  diagnostic  allows fast  recharge  and  recovery  of  deep  discharged 
batteries,  adding  value  and  reliability  to  the  system  hosting  the  CB  device.  The  type  of  charging  is  Voltages 
stabilized and Current stabilized IUoUo. 
Four charging modes are identified by a flashing code on a Diagnosis LED. 
To maintain the Output Load in lower Voltage state, don’t put jumper in position 4, in this case no boost charge 
but only Float charge. 
 

 

State 

Diagnosis LED 

Battery Fault 
LED 

Charging Type 

Trickle/Float 

1 Blink/ 2 sec 

OFF 

Absorption 

1 Blink/sec 

OFF 

Boost/Bulk 

2 Blink/sec 

OFF 

Recovery 

5 Blink/sec 

OFF 

  
 

 

 

Battery Care 

The  Battery  Care  philosophy  is  base  on  algorithms  that  implement  rapid  and  automatic  charging,  battery  charge 
optimization  during  time,  flat  batteries  recovery  and  real  time  diagnostic  during  installation  and  operation.  The  Real 
Time Auto-diagnostic  system, monitoring  battery faults  such  as,  elements  in  short circuit,  accidental  reverse  polarity 
connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis 
Led; during the installation and after sell. Each device is suited for all battery types, by means of jumpers it is possible 
setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option).They guarantees battery reliability 
in time by continuously testing the internal impedance status, avoids any possible risk of damages and grants also a 
permanent, reliable and safe connection of the battery to the power supply. The system, through a battery stimulation 
circuit  with  algorithms  of  evaluation  of  the  detected  parameter,  is  able  to  recognize  batteries  with  a  short-circuited 
element. Battery test: Automatic.  