035-18200-000-B-1102
Unitary Products Group
5
TABLE 1: PHYSICAL DATA
DESCRIPTION
UNIT MODEL
FHP180
FHP240
Coil
Rows Deep X Rows High
3 X 32
3 X 32
Finned Length - inches
54.5
83
Face Area - square feet
12.11
18.44
Tube (Copper) OD - inches
3/8
3/8
Fins (Aluminum) per inch
13
13
Centrifugal Blower (Forward Curve) - Qty
Diameter X Width - inches
18 X 18 - 1
15 X 12 - 2
Blower Motor
1
HP
3
---
RPM
1750
---
Filters (Throwaway)
Quantity per unit
6
8
Size (in)
20 X 20 X 1
20 X 22 X 1
Total Face Area - square feet
16.7
24.1
Unit Weight (lbs)
Shipping
425
830
Operating
435
720
Accessory Operating Weight (Lbs.)
Motor & Drive
3 HP
90
90
5 HP
---
120
Electric Heat
10 KW
63
---
20 KW
66
126
30 KW
71
129
40 KW
---
132
50 KW
80
137
Supply Air Plenum
114
150
Return Air Grille
20
15
Base
100
120
1.
Refer to “Blower Motor and Drive Data” table for more information.
TABLE 2: UNIT APPLICATION DATA
APPLICATION LIMITATIONS
MIN
MAX
VOLTAGE VARIATION (208/230-3-360)
187
253
VOLTAGE VARIATION (460-3-360)
414
506
AMBIENT AIR ON OUTDOOR COIL (COOLING CYCLE) °f
45
115
AMBIENT AIR ON INDOOR COIL (COOLING CYCLE) °F
68
86
AMBIENT AIR ON OUTDOOR COIL (HEATING CYCLE) °F
0
70
AMBIENT AIR ON INDOOR COIL (HEATING CYCLE) °F
60
80