5490689-LTG-F-0620
Johnson Controls Unitary Products
41
APPLICATIONS AND ACCESSORIES
Refer to Price Manual for specific model numbers.
* For Low Ambient and/or Long Lineset Applications, please see the acces-
sories listed below.
Non-Standard Lineset Applications -
For installations with
reduced diameter or long linesets, refer to the current version of
the Piping Application Guide P/N 247077, available in the Appli-
cation Bulletins section on
www.simplygettingthejobdone.com
.
Start Assist Kit S1-2SA067*****:
Provides increased compres-
sor starting torque for areas with low supply voltage. Required
for all units when applied with long linesets. See Price Pages or
Source1 SmartSearch for the correct kit for each application.
Support Feet S1-HPRKIT-**:
Kit of 5 support feet to raise unit
above snow or landscaping. Available in heights of 3", 6" or 12".
Anchor Bracket Ground Mount Kit S1-1HK0701:
Firmly
anchors unit to pad or support structure. When properly
installed, approved for ground-mounted applications.
Anchor Bracket Roof Mount Kit S1-1HK0901:
Firmly anchors
unit to pad or support structure. When properly installed,
approved for roof-mounted applications.
Indoor TXV Kit S1-1TVM***:
Thermal expansion valves pre-
cisely meter refrigerant for optimum performance over a wide
range of conditions. See System Charge Table & Price Pages
for TXV part number for each AC & HP model.
Wall Mount Kit (S1-ACB-**):
Includes two brackets to allow
outdoor unit to be securely mounted to a vertical wall. Mounting
hardware is field sourced according to the specific application.
Winter Cover Kit S1-CCVRE***:
Custom fit winter cover pro-
tects AC condensing unit from debris during the off-season.
Must be removed prior to unit operation. See Price Pages for
the correct cover for each application.
Cold Weather Charging Tent S1-CHGTENT01:
Provides
warm environment to accurately service AC & HP systems in
ambient conditions 55ºF (13ºC) or colder.
Touch-up Paint S1-5130153****:
Color matched aerosol paint
for touching up unit chassis and panels. See Price Pages or
Source1 SmartSearch for the correct color for each application.
Thermostat:
Compatible thermostat controls are available
through accessory sourcing. For optimum performance, these
outdoor units are fully compatible with our Luxaire Hx™ Touch-
screen Thermostats available through Source1. For more infor-
mation, see the thermostat section of the Offering Catalog.
Rated in accordance with ARI Standard 270.
Rated in accordance with ARI Standard 270.
Standard Application Limits*
Maximum Lineset Equivalent Length
80 Ft
Outdoor Ambient Temperature Limits
Cooling Operation
Maximum DB
125°F
Minimum DB
35°F
Heating Operation
Maximum DB
75°F
Minimum DB
-20°F
SOUND POWER RATINGS - COOLING
Stage 1 - Cooling
Octave Band Sound Power Level (db re. 1-pW)
Model Number
63
125
250
500
1000
2000
4000
8000
dBA
SQI
HL19B2421S
66
67
60
62
64
55
51
46
66
19.0
HL19B3621S
66
67
61
66
66
57
51
50
68
19.0
HL19B4821S
67
68
65
68
69
58
54
51
71
19.0
HL19B6021S
68
72
68
70
69
62
56
54
72
19.0
Stage 2 - Cooling
Octave Band Sound Power Level (db re. 1-pW)
HL19B2421S
66
66
61
66
66
57
51
49
68
19.0
HL19B3621S
68
72
68
70
70
62
56
54
72
19.0
HL19B4821S
75
70
68
70
69
63
56
53
73
19.0
HL19B6021S
67
72
70
72
70
62
57
53
73
19.0
SOUND POWER RATINGS - HEATING
Stage 1 - Heating
Octave Band Sound Power Level (db re. 1-pW)
Model Number
63
125
250
500
1000
2000
4000
8000
dBA
SQI
HL19B2421S
65
65
61
66
63
53
50
47
67
19
HL19B3621S
68
70
67
70
68
60
56
52
71
19
HL19B4821S
65
65
64
67
68
58
54
48
70
19
HL19B6021S
66
66
62
69
66
59
56
56
70
19
Stage 2 - Heating
Octave Band Sound Power Level (db re. 1-pW)
HL19B2421S
66
70
66
68
68
59
56
51
71
19
HL19B3621S
68
72
67
70
69
61
56
54
72
19
HL19B4821S
67
71
70
72
70
62
56
53
73
19
HL19B6021S
75
72
67
70
71
62
56
52
73
19