Redundant I/O Modules
▪
Digital Outputs
50
11.3.3
Technical Data
Inputs 24...110 V Modules
Number
6 (1, 2 potential A; 3,4 potential B;
5,6 potential C)
Data capacity in the process image
2x1 byte outputs
2x2 byte inputs
Current consumption at DC 24 V
nom. 125 mA
(per L-Bus Connection)
Electrical isolation
Isolating voltage
▪
AC 1.5 kV outputs and
electronics
▪
AC 1.5 kV potentials against
each other
Output voltage
DC 24...110 V (16.8...137.5 V)
protected against polarity reversal
Output current
max. 0.5 A per channel
Channel Type
N-MOS FET
Safety Function
inverse, short-circuit proof
(switching off after 80 µs), abnormal
temperature protection
External Fuse
B4
Module Status Flag
Is not used in this module (always
“0“). The outputs are read back on
the connectors (1st input byte).
The error status of the output driver
are shown in the 2nd input byte
(“0“=no mistake, “1“ = overload).