10.6.10 Activating the Release code
If the
Release code
is activated, the dosing pump is protected
against unauthorized access. You can only create settings after you
enter the correct
Release code
.
You can set any
Release code
you like from 0000 to 9999.
1.
Use the
or
key to choose the
Release code
menu item and
press
Setup
.
The dosing pump displays menu 6.10
Release code.
Fig. 10-9: Release code
2.
Use the
+
and
-
keys to set a value of 0 to 9 for the first digit of the
code and then press
Next
.
3.
Proceed as described under point 2 for the other digits.
4.
Choose the last item
Off
and press
+
.
5.
Press
Back
.
The
Release code
is activated. The dosing pump displays the
corresponding symbol:
Start screen with activated Release code
10.6.10.1 Entering the Release code
Once you press any key, you must enter the
Release code
. If you
enter the code correctly, you have 120 seconds in which to operate the
dosing pump. When the 120 seconds have elapsed, you must re-enter
the
Release code
, even if you are in the middle of making another
entry (this does not include settings in the menus).
Fig. 10-10: Entering the Release code
1.
Use the
+
and
-
keys to set a value of 0 to 9 for the first digit of the
code and then press
Next
.
2.
Proceed as described under point 1 for the other digits.
3.
After entering all the digits, press
OK
.
If your input is correct, the dosing pump displays the start screen
.
10.6.10.2 Deactivating the Release code
1.
Press
Menu
.
2.
Use the
or
key to choose the
System setup
menu item and
press
OK
.
3.
Use the
or
key to choose the
Release code
menu item and
press
Setup
.
4.
Keep pressing
Next
until
On
is selected.
5.
Press
-
.
6.
Press
Back
.
Release code deactivated.
10.6.11 Activating the Safety code
Protects the
System setup
menu from unauthorized access. In the
factory default setting, the code is not activated.
You can set any
Safety code
you like from 0000 to 9999.
1.
Use the
or
key to choose the
Safety code
menu item and
press
Setup
.
The dosing pump displays menu 6.11
Safety code.
Fig. 10-11: Safety code
2.
Use the
+
and
-
keys to set a value of 0 to 9 for the first digit of the
code and then press
Next
.
3.
Proceed as described under point 2 for the other digits.
4.
Choose the last item
Off
and press
+
.
WARNING
Caustic burns or other burns through dosing media!
If the Release code is activated, operation of the dosing pump is
blocked. If a dosing pump has been started without the Release
code being entered, it can only be stopped by means of the power
supply. In unfavourable cases, if the user has inadvertently acti-
vated or forgotten the release code, the dosing pump cannot be
quickly stopped and injuries may result.
Install an emergency stop switch or integrate the dosing pump
into the plant safety concept.
Release code
4 3 2 1 Off
Back
6.10
Next
-
+
Manual mode
Liter
day
0.0%
0.00
If you have forgotten the code, please contact Lutz-Jesco
GmbH.
Release code
1 1 1 1
Back
8.1
Next
-
+
i
Safety code
1 2 3 4 Off
Back
6.11