Technical data
Rating plate
13
© Lutz-Jesco GmbH 2016
Subject to technical changes.
160520
BA-20901-02-V01
Chlorinator C 2526
Operating instructions
5 Technical data
Description
Value
dosage range
5 / 10 / 15 / 25 kg/h Cl
2
Operating vacuum
- 100 mbar
Required injector vacuum
- 250 mbar
Adjustable flow
0 – 100 %
Flow meter
Length
300 mm
Accuracy
± 2 % of final scale reading
Scale ratio
1:20
Material
Glass
Vacuum meter
Measuring range
-1 – 0 bar
Size
Ø63 mm
Accuracy
± 2.5 % of final scale reading
Load capacity of optional contacts
50 V / 0.5 A / 10 W
Material in contact with the media
plastics
PVC, PMMA
Springs
Hastelloy
seals, diaphragms
FPM
Weight with electrical regulation
valve and signal converter
Wall device
approx. 15 kg
Free standing cabinet
approx. 43 kg
Ambient temperature
0 – 40 °C (avoid direct sunlight)
Air humidity
max. 95%, non condensing
Table 7: Technical data
i
The technical data for the electrical regulation valve and the
signal converter are listed in the appendant documentation.