14
AC motor does not move in either
direction when manual override
buttons pressed.
• Motor wired to Group Controller
improperly.
• Limit switches on motor not set
properly.
• Motor Supply Jumper terminal is not
jumpered to 120 V terminal.
Verify motor wiring.
Verify limit switch settings on motor.
Place a jumper wire of sufficient wire
gauge between Motor Supply Jumper
and 120 V Input Voltage terminals.
See page 6.
Troubleshooting
Motors cannot be controlled from low-
voltage contact closure inputs but
operate properly with the manual
Open/Close buttons.
• Contact closure miswire.
Verify connections on contact closure
inputs.
Motors only move while low-voltage
contact closure is applied.
• Options Switch #5 in ON position.
Change position of Options Switch #5
to OFF. See page 11.
Motor moves in the wrong direction.
• Options Switch not set properly.
Reverse the corresponding Options
Switch. See page 7.
Symptom
Possible Cause
Solution