Contact Closure Inputs:

Maintained Mode Operation

In maintained mode, the Switched Live output for a
channel, for instance SW Live 1A, is energized only while
the contact closure is provided to the input for that
channel. As soon as the contact closure is removed from
the input, the Switched Live output is de-energized. This
gives rise to possible conflicts if a contact closure is
provided during the time another contact closure is
provided. Below are descriptions of how the Group
Controller addresses these situations.

Inputs on a single channel

When a contact closure is provided to a single input on an
individual channel, the Group Controller will energize the
appropriate Switched Live output. If a contact closure is
then provided to another input on that same channel while
the first contact closure is provided, the Group Controller
will recognize this combination as a request to stop. This
will happen regardless of how much time elapses between
the application of the two contact closure inputs.

For example, if a contact closure is provided to Close 1,
the Group Controller will energize the Switched Live
output to close the AC motor on Channel 1. If a contact
closure is provided to Open 1 while a contact closure is
still provided to Close 1, the Group Controller will de-
energize the Switched Live output on Channel 1, stopping
the AC motor.

If contact closures are provided to both the Open and
Close inputs on a particular channel, the Group Controller
will de-energize the Switched Live outputs for that
channel. If one of the contact closures is then released,
the Group Controller will NOT recognize that as a request
to move the AC motor to the position indicated by the
contact closure that is still provided. Instead, the Group
Controller will leave the Switched Live outputs de-
energized. In order for the Group Controller to recognize a
new input signal, the contact closure must be removed
and then provided again.

Note: It is not recommended to connect two or more
contact closure devices on the same channel if
Momentary mode is selected. If this is done, it is possible
for a channel to become unresponsive to inputs if contact
closures are provided by the two devices at the same
time.

For instance, if one device provides a contact closure to
the Open input, the Group Controller energizes the
Switched Live output that opens the AC motor. If the
second device then provides a contact closure to the
Close input, the Group Controller will then de-energize the
Switched Live output, stopping the AC motor. At this point,
both contact closures must be removed before the Group
Controller will recognize a new request.

If it is desired to connect two or more contact closure
devices on the same channel, use Maintained mode.

Inputs on a single channel and Master Control

When a contact closure is provided to a single input on an
individual channel, the Group Controller will energize the
appropriate Switched Live output. If a contact closure is
then provided to a Master Control input while the first
contact closure is still provided, the Group Controller will
energize the Switched Live outputs requested by the
Master function on all channels of the Group Controller.

For example, if a contact closure is provided to Close 1,
the Group Controller will energize the Switched Live
output to close the AC motor on Channel 1. If a contact
closure is then provided to the Master Open input while a
contact closure is still provided to the Close 1 input, the
Group Controller will energize the Switched Live outputs
to open the AC motor on all channels.

When a contact closure is provided to a Master Control
input, the Group Controller will energize the appropriate
Switched Live outputs on all channels of the Group
Controller. If a contact closure is then provided to a single
input on an individual channel while the Master Control
contact closure is still provided, the Group Controller will
activate the Switched Live output requested by the
individual input, while keeping the Switched Live output in
the same state for the other three channels.

For example if a contact closure is provided to the Master
Open input, the Group Controller will energize the
Switched Live outputs to open the AC motor on all
channels. If a contact closure is then provided to the
Close 1 input, the Group Controller will energize the
Switched Live output on Channel 1 to close the AC motor
on Channel 1, but continue energizing the Switched Live
outputs on Channels 2, 3 and 4

Appendix A

Summary of Contents for WC-2M-GC

Page 1: ...uide for Installing Operating and Maintaining a Lutron AC Motor Group Controller Please Read Before Installing Models WC 2M GC 2 Motor Controller WC 4M GC 4 Motor Controller AC Motor Group Controller Installer s Guide ...

Page 2: ...eaker or remove fuse before installing and wiring the controller Do not wire with power ON Operating environment should be between 32 F to 104 F 0 C to 40 C Proper short circuit protection and overload protection must be provided at the distribution panel You can use up to a 20 A breaker for your application where applicable Description The WC 2M GC and WC 4M GC Group Controllers are designed to c...

Page 3: ... Motor Wiring 3 conductors plus ground Line Voltage Wiring AC Motor Group Controller Coopersburg PA 18036 USA www lutron com WC 4M GC 4 MOTOR GROUP CONTROLLER 110 127 V 60 Hz 20 A Max Input Current LOAD TYPES Single Phase Bi directional Motor 5 A 1 4 HP per Channel at 120 V TYPES DE CHARGES Phase Simple Moteur Bidirectionel 5 A 1 4 HP par Canal a 120 V Listed 243C Ind Cont Eq Questions Call Lutron...

Page 4: ...ive 3A Neutral SW Live 4B SW Live 4A Neutral 9 5 in 12 in 6 2 in 1 25 in 7 9 in 735 in AC Motor Group Controller Coopersburg PA 18036 USA www lutron com 500 9575 Rev B WC 4M GC 4 MOTOR GROUP CONTROLLER 110 127 V 60 Hz 20 A Max Input Current LOAD TYPES Single Phase Bi directional Motor 5 A 1 4 HP per Channel at 120 V TYPES DE CHARGES Phase Simple Moteur Bidirectionel 5 A 1 4 HP par Canal a 120 V Li...

Page 5: ...t kit please refer to the instructions provided with the kit Testing motor wiring using a SPDT switch 1 Turn power OFF at circuit breaker MCB or remove fuse 2 Connect the motor ground wire to earth ground Connect earth ground to the ground terminal on the switch 3 Connect the motor neutral wire to supply neutral 4 Using one momentary Single Pole Double Throw SPDT switch for each motor connect hot ...

Page 6: ...e is 9 0 in lbs for line voltage connections and 10 in lbs for earth ground connections Run all power feed and motor power wiring through the knockout holes on the sides of the unit Wiring Detail Neutral 120V 240V Motor Supply SW Live 1B SW Live 1A Neutral SW Live 2A Neutral Power Feed Wiring Motor 1 Power Wires SW Live 1B SW Live 1A Neutral Neutral 120 V Input Motor Supply Jumper Wiring Overview ...

Page 7: ...r to unit Once the appropriate line voltage and motor connections have been made to the unit replace the cover on the line voltage wiring compartment Remove the cover from the Class 2 wiring compartment Turn power back ON 2 Determine AC motor position Determine whether the AC Motor that is controlled by Channel 1 is open or closed If it is open press the Close 1 manual override button If it is clo...

Page 8: ...icated stop input In this wiring example the stop function is achieved by simultaneously providing a closure on the open and close terminals of the input terminal block No connection is made to the stop terminal on the input terminal block Contact closure inputs 3 and 4 are only available on the WC 4M GC ler SA 500 9575 Rev B ROLLER l Motor 120 V rectionel 0 V al Support Class 2 COM Open Stop Clos...

Page 9: ... stop terminal of the input terminal block WC 4M GC Group Controller Shown Class 2 PELV Wiring Com 1 Open 1 Stop 1 Close 1 Com 2 Open 2 Stop 2 Close 2 Com 3 Open 3 Stop 3 Close 3 Com 4 Open 4 Stop 4 Close 4 Contact closure inputs 3 and 4 are only available on the WC 4M GC ler SA 500 9575 Rev B ROLLER l Motor 120 V rectionel 0 V al Support Class 2 COM Open Stop Close COM Open4 Stop4 Close4 COM Open...

Page 10: ...SE 3 OPEN 2 CLOSE 2 OPEN 1 CLOSE 1 WC 4M GC Group Controller Shown Class 2 PELV Wiring Com Open All Stop All Close All Input controls channel 1 motor only optional Input controls channel 2 motor only optional Input controls channels 3 and 4 motors only optional Input simulta neously controls all four channels Contact closure inputs 3 and 4 are only available on the WC 4M GC ler SA 500 9575 Rev B R...

Page 11: ...GC Group Controller Shown Input controls channels 1 and 2 motors on this unit only Input simultaneously controls all four channels on all units parallel wired together Note When connecting multiple Group Controllers in parallel make sure the contact closure device is rated for the total amount of current delivered by each Group Controller total current 2 mA times the number of Group Controllers Ex...

Page 12: ...lose contact closure is received or when another contact closure is received whichever comes first The relays will open immediately upon receiving the stop contact closure Maintained Inputs The power relays remain closed as long as the input closure remains closed However the most recent command received will be executed even if the previous contact closure is still maintained Momentary or maintai...

Page 13: ...if contact closures are provided by the two devices at the same time For instance if one device provides a contact closure to the Open input the Group Controller energizes the Switched Live output that opens the AC motor If the second device then provides a contact closure to the Close input the Group Controller will then de energize the Switched Live output stopping the AC motor At this point bot...

Page 14: ...mper and 120 V Input Voltage terminals See page 6 Troubleshooting Motors cannot be controlled from low voltage contact closure inputs but operate properly with the manual Open Close buttons Contact closure miswire Verify connections on contact closure inputs Motors only move while low voltage contact closure is applied Options Switch 5 in ON position Change position of Options Switch 5 to OFF See ...

Page 15: ...15 Notes ...

Page 16: ...RANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE THIS WARRANTY DOES NOT COVER THE COST OF INSTALLATION REMOVAL OR REINSTALLATION OR DAMAGE RESULTING FROM MISUSE ABUSE OR IMPROPER OR INCORRECT REPAIR OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION THIS WARRANTY DOES NOT COVER INCIDENTAL OR CONSEQUENTIAL DAMAGES LUTRON S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION ...

Reviews: