S P E C I F I C AT I O N S U B M I T TA L
Page
Job Name:
Job Number:
Model Numbers:
Vive
HMS-0, HMS-1, HMS-2
Wireless Hub
3691044-04g 7 03.23.21
Range Diagrams
22 m
Maximum
22 m
Maximum
30 m
30 m
Range with multiple Vive hubs
All wireless devices to be associated to the Vive hub must be within 22 m of the Vive hub and must be on the same
floor as the Vive hub.
Note:
Vive hubs should be mounted greater than 3 m apart on the same floor.
Note:
Lutron requires that the Vive hub not be installed above metal ceilings or tiles with a metal backing.
Note:
A corporate Wi-Fi network can interfere with the Wi-Fi on the Vive hub. Where a corporate Wi-Fi network exists,
it is recommended to do the following:
• Connect the Vive hub to the corporate network using the Ethernet connection on the hub and disable Wi-Fi on
the hub.
Note:
Vive hubs should be mounted greater than 3 m from a Wi-Fi router or access point.
30 m
30 m
Private Office
PowPak Dimming
Module
Conference Room
PowPak Dimming Module
Open Office
PowPak Relay Module
Personal Control
Pico Remote Control
Sensors
Radio Powr Savr
Occupancy Sensor
Setup, Monitor
and Control
Vive Hub
9 m
Maximum
1
9 m
Maximum
1
9 m
Maximum
1
9 m
Maximum
1
22 m
Maximum
Vive Hub RF
coverage
1
NOTE:
Wireless sensors and controls must be located within
9 m of the associated control module.
• Metal ceiling grids must have a > 3 mm gap of non-metal
material which extends the entire length of the tile on at least
one edge. This is often achieved by foam spacers that are
used to prevent tile-to-tile rattling.
• Metal ceiling grids which are continuous (with no gap) or those
that are interlocked, must have a total surface area that is
less than 81 m
2
for each section. The overall space can be
larger as long as there are non-metal sections bordering or
intersecting the metal sections.
7