S P E C I F I C AT I O N S U B M I T TA L
Page
Job Name:
Job Number:
Model Numbers:
Vive
HMS-0, HMS-1, HMS-2
Wireless Hub
3691044-04g 4 03.23.21
Specifications
Regulatory Approvals
• SRRC
• CCC (Power Supply)
Power / Performance
• Input to power supply:
220 – 240 V
~
50 / 60 Hz 0.6 A
• Input to Vive hub:
24 V
-
350 mA
System Limits
• HMS-1, HMS-2 support up to 700 Lutron Wireless
devices. HMS-0 supports 75 Lutron Wireless devices.
• Any given load device can be controlled by 10 occupancy
sensors, 10 Pico remote controls and 1 daylight sensor
(Pico remote controls and sensors must be located within
9 m of the load device they are controlling).
Metal Ceiling Mounting
• Metal ceiling grids must have a > 3 mm gap of non-metal
material which extends the entire length of the tile on at
least one edge. This is often achieved by foam spacers
that are used to prevent tile-to-tile rattling.
• Metal ceiling grids which are continuous (with no gap) or
those that are interlocked, must have a total surface area
that is less than 81 m
2
for each section. The overall space
can be larger as long as there are non-metal sections
bordering or intersecting the metal sections.
• Do not install the Vive hub above metal ceilings or tiles
with a metal backing.
Mounting
• Use surface-mount version for mounting to a hard or
cement ceiling.
• Power supply mounts to a Lutron-supplied US-style
101.6 mm x 101.6 mm (4 in x 4 in) junction box.
• Power supply must be mounted within 30 m of the Vive
hub. Wiring should be 0.2 mm
2
to 2.5 mm
2
(24 AWG to 12 AWG).
Environment
• For indoor use only.
• 0 °C to 40 °C.
• Relative humidity less than 90% non-condensing.
Contact Closure Input Terminals
• First contact closure input (CCI 1) is to be used for
initiating load shed only.
• The second contact closure input (CCI 2) may be
programmed to activate a scene.
If activating a scene, a "deactivation" behavior may be
set in the scene in order to set two behaviors for the
one input.
• Accepts only maintained inputs.
• Off-state leakage current must be less than 100 μA.
• Open circuit voltage: 24 V
-
maximum.
• Input wiring: 0.2 mm
2
to 2.5 mm
2
(24 AWG to 12 AWG).
• Contact Closure Inputs on multiple hubs can be wired
in parallel. DO NOT wire inputs in parallel with other
equipment as it can cause the inputs on either of the
devices to falsely trigger.
• Up to 4 hubs in parallel.
• To ensure proper operation of Contact Closure Inputs,
a PS-M-20W-240 power supply may not be used to
provide power to more than one hub.
• Inputs must be dry contact closure, solid state, open
collector, or active-low (NPN) / active high (PNP) output.
– Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
– Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
Programming
• The Vive Hub is meant to be permanently installed. It
is not intended to be used as a programming tool that
can be removed from the site after commissioning.
Various Vive system features are dependent on the
hub for proper functionality. In addition, users and
other maintainers will be forced to recommission the
entire system in order to make simple changes or
additions if the hub is not installed on-site as part of the
commissioned system.
Warranty
• 2 year limited warranty. The customer can register the
product to increase the warranty period from
2 year to 5 years. Please visit
www.lutron.com/en-US/ResourceLibrary/warranty/
Limited%20Comm.pdf for warranty details.
4