background image

®

S P E C I F I C AT I O N   S U B M I T TA L

Page

Job Name:

Job Number:

Model Numbers:

Vive

HMS-0, HMS-1, HMS-2

Wireless Hub

3691044-04g   10   03.23.21

X

Vive

Dedicated Network

Wi-Fi Only

  Ports Used

• 

No IT configuration needed

Corporate Network

Single Hub

Security 1

Link segment 100 m

Building Management System (BMS)

Vive Hub

Vive Hub

Corporate Wi-Fi 

Router

Ports Used

Traffic

Port

Type

Connection

Description

Outbound

47808  

(configurable)

UDP

Ethernet

Used for BACnet

®

 integration into Building Management Systems

80

TCP

Used to discover the Vive hub when mDNS is not available

5353

UDP

Ethernet

Used to discover the Vive hub via mDNS

Configurable

TCP

Ethernet

Used for OpenADR

R

. Specified by utility company

Inbound

443

TCP

Both Ethernet and 

Wi-Fi

Used to communicate with software update server

80

TCP

Used by other Vive hubs to proxy

8081

TCP

Ethernet

Used for local LEAP connections to integrations and Vive Vue

8083

TCP

Ethernet

Used for local LAP connections to integrations and Vive Vue

8444

TCP

Ethernet

Used to communicate with the Vive Vue server

47808  

(configurable)

UDP

Ethernet

Used for BACnet

®

 integration into Building Management Systems

5353

UDP

Ethernet

Used to discover the Vive hub via mDNS

X

Vive

10

Summary of Contents for Vive HMS-0

Page 1: ...multi color LED provides feedback on what mode the hub is in Connects directly to any smartphone tablet or computer using built in Wi Fi 2 4 GHz 802 11b g using WPA2 Security Ethernet 10 100 Mbps con...

Page 2: ...holidays Allows scheduling events on specific day of the year Provides calculated energy data for PowPak modules Create and edit areas Tune area light levels by trimming the high end and low end outp...

Page 3: ...pp Maximum of 50 scenes are supported Requires Vive hub software 01 13 or higher Programmable CCI The second contact closure input CCI 2 can be programmed to activate a scene Scene activation o Set a...

Page 4: ...re Input Terminals First contact closure input CCI 1 is to be used for initiating load shed only The second contact closure input CCI 2 may be programmed to activate a scene If activating a scene a de...

Page 5: ...Hub Model Numbers includes power supply and mounting adapter HMS 0 FM Starter Vive hub flush mount adapter and power supply HMS 1 FM Vive hub flush mount adapter and power supply HMS 2 FM Premium Viv...

Page 6: ...re shown as mm Surface mount Adapter Details Knockouts for conduit Vive Hub Top View Side View 173 135 71 38 Flush mount Adapter Top View Side View 165 79 Surface mount Adapter Top View Side View 122...

Page 7: ...b Note Vive hubs should be mounted greater than 3 m from a Wi Fi router or access point 30 m 30 m Private Office PowPak Dimming Module Conference Room PowPak Dimming Module Open Office PowPak Relay Mo...

Page 8: ...tyle junction box Supplied US style junction box Vive hub Flush mount adapter Vive Hub CCI1 COM 24 V COM CCI2 Red Blue Ethernet 10 100 LAN 24 V 220 240 V Ceiling Power supply Vive hub Surface mount ad...

Page 9: ...rest technologies The Vive hub can be deployed in one of two ways Dedicated Lutron Network Connected to the corporate IT network via Ethernet The Vive hub must be connected via Ethernet to access cer...

Page 10: ...ed to discover the Vive hub when mDNS is not available 5353 UDP Ethernet Used to discover the Vive hub via mDNS Configurable TCP Ethernet Used for OpenADRR Specified by utility company Inbound 443 TCP...

Page 11: ...ommunication link Inter Hub Link Wiring Security 1 continued Link segment 100 m Ports Used Traffic Port Type Connection Description Outbound 47808 configurable UDP Ethernet Used for BACnet integration...

Page 12: ...LB P LRF4 OHLB P LRF4 OWLB P In Line Phase Control Dimmers2 RMMS 250 NE The Lutron logo Lutron Lutron Clear Connect Pico PowPak Radio Powr Savr Vive Vue and Vive are trademarks or registered trademark...