24 V
~
45 mA
24 V
-
35 mA
CCO
Status
LED
CCO Toggle
Advanced
Operations
Contact
Closure
Output
(CCO)
Test
Link
Cal.
+
All Wireless Transmitters must be installed within
10 m of the PowPak
R
CCO Module.
12 m
10 m
Note:
CCO Module supply wires can be
connected in any polarity.
Conduit Nut
Note:
When wiring CCO output,
use 0.5 to 1.5 mm
2
(20 to 16 AWG)
solid or stranded wire.
To CCO-controlled device.
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
Supply Voltage
24 V
~
/ 24 V
-
21 mm
knockout
opening
Wiring a Lever Operated Connector (shown)
When wiring lever operated
connectors (2 supplied) use
2.5 mm
2
to 4.0 mm
2
(14 to 12 AWG) solid or
stranded copper wire.
For Model No.
RMN-CCO1-24-B
use
supplied Twist-on wire connectors.
(2 supplied)
1
2
3
10 mm
Associate Wireless Transmitters to PowPak
R
CCO Module
2
On the PowPak
R
CCO
Module, hold the CCO
toggle button for 6 seconds
to enter association mode.
A
Note:
The CCO will open and close
once after each step to confirm
successful completion.
Before beginning this step, make sure that there are no other PowPak
R
modules being set up within the same building.
It is possible that Wireless Transmitters from other systems can be incorrectly associated to this system.
B
C
Hold the indicated button on a Wireless Transmitter for
6 seconds to associate the device.
Repeat for any additional Wireless Transmitters.
Hold the CCO Toggle button on the PowPak
R
CCO
Module for 6 seconds to save association(s).
Test
Link
Cal.
Daylight Sensor setup
4
Turn lights in room on using the CCO Toggle
button on the PowPak
R
CCO Module or an
associated Pico
R
Wireless Control.
Press & hold “Cal.” on the associated
Daylight Sensor for 6 seconds.
Exit room for 5 minutes to allow
calibration to be completed.
A
B
C
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple CCO Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight
Sensor
(LRF3-DCRB, LRF5-DCRB)
installation
instructions.
Use the CCO Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
Calibration
Tuning (Optional)
Note:
When calibration has completed, all lights
will flash and the system will begin daylighting.
Note:
Only complete step 4 if using a Daylight Sensor with the CCO Module
to control a device that is switching a lighting source.
Test
Link
Cal.
Permanently Install
Wireless Transmitters
3
Note:
Please consult individual component
installation guides for information.
Test
Link
Limited Warranty
Lutron EA Ltd. (“Lutron EA”) warrants each unit to be free from defects in
material and workmanship and to perform under normal use and service.
To the extent permitted by law, Lutron EA and Lutron Electronics Co. Inc.
(“Lutron”) make no warranties or representations as to the units except as
set forth herein. This warranty shall run for a period of two years from the
date of purchase and Lutron’s obligations under this warranty are limited to
remedying any defect, replacing any defective part or replacement (at Lutron
EA’s sole option) and shall be effective only if the defective unit is shipped
to Lutron EA postage prepaid within 24 months after purchase of the unit.
Repair or replacement of the unit does not affect the expiry date of the
warranty. This warranty does not cover damage or deficiencies due to abuse,
misuse, inadequate wiring or insulation or use or installation other than in
accordance with instructions accompanying the unit.
To the extent permitted by law, neither Lutron EA nor Lutron shall be liable
for any other loss or damage including consequential or special loss or
damages, loss of profits, loss of income, or loss of contracts arising out of
or relating to the supply of the unit or the use of the unit and the purchaser
assumes and will hold harmless Lutron EA and Lutron in respect of all such
loss or damage. Nothing in this warranty shall have the effect of limiting or
excluding Lutron EA’s or Lutron’s liability for fraud or for death or personal
injury resulting from its own negligence, or any other liability, if and to the
extent that the same may not be limited or excluded as a matter of law.
This warranty does not affect the statutory rights of consumer
purchasers of this product.
Although every attempt is made to ensure that catalogue information is
accurate and up-to-date, please check with Lutron EA before specifying or
purchasing this equipment to confirm availability, exact specifications, and
suitability for your application.
Lutron, Pico, PowPak, Energi TriPak and are registered trademarks and
Radio Powr Savr is a trademark of Lutron Electronics Co., Inc.
©2012 Lutron Electronics Co., Inc.
CCO-controlled
device does
not respond
to Wireless
Transmitter(s).
t
Ensure power to the PowPak
R
CCO
Module is properly applied.
t
Ensure the CCO-controlled device has
been properly wired to the PowPak
R
CCO Module.
t
Ensure Wireless Transmitter is properly
associated to PowPak
R
CCO Module.
t
Ensure that the Wireless Transmitter
battery is installed correctly.
Wireless
Transmitter(s)
cannot be
associated to
PowPak
R
CCO
Module.
t5IFNBYJNVNOVNCFSPG8JSFMFTT
Transmitters have been associated to
the PowPak
R
CCO Module. To remove
a previously set up Wireless Transmitter,
tap the button used for association on
the Wireless Transmitter three times, on
the third tap hold for three seconds and
then tap three more times.
Troubleshooting
Reset Factory Defaults
Note:
In some instances it may be necessary to reset the
PowPak
R
CCO Module back to factory default settings.
A
Triple-tap the Advanced Operations button, “ADV”
on the PowPak
R
CCO Module and hold until the
LED begins to flash slowly.
Within 3 seconds of flashing, release and triple-tap
the button again and the LED will flash rapidly
indicating that the unit has been reset to factory
defaults.
B
Note:
Any associations or programming previously set
up with the unit will be lost and will need to be
re-programmed.
Unaffected Mode
Unaffected mode allows a system with an Occupancy Sensor
associated to multiple CCO Modules to be set up such that only
selected loads turn on automatically. Other loads will require a
manual turn-on with a Pico
R
Wireless Transmitter. All loads will turn
off automatically when the room is vacated.
A
B
C
On a CCO Module, press and hold both the CCO
Toggle and Advanced Operations (“ADV”) buttons for
6 seconds until the LED begins flashing quickly.
On the associated Occupancy Sensor, press and hold
the “Test” button* for 6 seconds until the lens flashes.
Unaffected mode will be exited automatically. This
CCO Module will now be unaffected by occupancy
commands. Repeat procedure for any additional
devices.
* If no “Test” button, hold “Lights On” button.
CCO Information
t
This product features a single contact closure output with both normally
open (NO) and normally closed (NC) dry contacts.
t
The CCO incorporates maintained output behavior only.
t
The CCO is rated to switch resistive loads at
voltages up to 24 V only. To properly control
inductive load types such as relays, solenoids,
or motors, refer to Application Note #434.
Switching
Voltage
0-24 V
-
0-24 V
~
Resistive
Load
1.0 A
0.5 A
R
Transmitting Device
Transmitted Command CCO Default Action
Pico
®
Wireless
Control
On
NO = Close, NC = Open
Off
NO = Open, NC = Close
Raise
No Action
Lower
No Action
Preset
NO = Close, NC = Open
Radio Powr Savr
TM
Occupancy Sensor
Occupied
NO = Close, NC = Open
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
TM
Vacancy Sensor
Occupied
No Action
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
TM
Daylight Sensor
Ambient light below
target level
NO = Close, NC = Open
Ambient light above
target level
NO = Open, NC = Close
Radio Powr
Savr
T
Occupancy
Sensor
10 m
Maximum
PowPak
R
CCO Module
Pico
R
Wireless
Control
Install in center of room to
maximize RF coverage.
www.lutron.com
English
Lutron EA Ltd | 6 Sovereign Close
London, E1W3JF, UK
PowPak
R
| Installation
CCO Module
Part of the Energi TriPak
R
Family
041399
Rev. A
12/2012
Important
Notes:
Please read before installing.
t
For installation by a qualified electrician in accordance with all local and
national electrical codes.
t
Note:
Use copper conductors only.
t
Check to see that the device type and rating is suitable for the application.
t
DO NOT
install if product has any visible damage.
t
If moisture or condensation is evident, allow the product to dry completely
before installation.
t
Operate between 0 °C and 55 °C.
t
0% to 90% humidity, non-condensing.
t
For indoor use only.
RMK-CCO1-24-B
RMN-CCO1-24-B
Need Help? www.lutron.com or call the Lutron Technical Support Center, at +44.(0)20.7680.4481
For each system ensure you have:
At Least One PowPak
R
CCO Module.
PowPak
R
CCO Module
Required Components
At least one Wireless Transmitter.
Radio Powr Savr
T
Occupancy/Vacancy Sensor
(6 maximum)
Radio Powr Savr
T
Daylight Sensor
(1 maximum)
Pico
R
Wireless
Control
(9 maximum)
The PowPak
R
CCO Module should
be installed using the mounting
tabs on the enclosure (screws not
provided). The PowPak
R
CCO Module
can be installed in a junction box or
marshalling box (optional) using the
conduit nut (provided). Consult local
and national electrical codes for
proper installation.
Install PowPak
R
CCO Module
1
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
Start Here