background image

PRO AV DLC Control Units 

operate up to six zones of lighting.
These units can control the intensity
of all the light sources in a room.
You can adjust the lights for any
activity with the press of a button or
from an AV Control System.

PLEASE LEAVE FOR OCCUPANT

PRO AV Digital Lighting Controller (DLC)
Installation Guide

Models

PAV6M-120/PAV6S-120

PAV6M-230/PAV6S-230

IMPORTANT!

Pro AV DLC lighting controls must be installed by a qualified electrician in accordance with all applicable regulations. Improper wiring can result in
personal injury or damage to Pro AV lighting controls or other equipment.

Always turn off circuit breaker/MCB or remove main fuse from power line before doing any work.

To avoid overheating and possible damage to equipment, do not install dimming devices to dim receptacles, motor-operated appliances, or dimmable
fluorescent lighting not equipped with Lutron Hi-Lume

®

, Eco-10

, or Tu-Wire

Electronic Dimming Ballasts.

When used with Low Voltage lighting, do not remove factory-installed bypass jumpers on load circuit terminals until load circuits are tested (see start-up
procedure on page 6.)

The Pro AV DLC dimming modules are designed to operate in ambient temperatures between 0 °C-40 °C (32 °F-104 °F).

To reduce the risk of overheating and possible damage to other equipment, the module must be mounted as shown. Failure to provide adequate space for
cooling may result in overheating and void the warranty.

Module hums slightly during operation and the internal relay clicks when the circuit is turned on and off. Choose an installation location where these
sounds are acceptable.

When used with low-voltage lighting, do not operate Pro AV DLC lighting controls with any lamps removed or burned out; Replace any burned out lamps
immediately. Use only low-voltage transformers that incorporate thermal protection or fused primary windings.

Pro AV DLC lighting controls are designed for commercial indoor use only.

T

his control uses Class 2/PELV wiring methods. Check with your local electrical inspector for compliance with national and local codes and wiring

practices.

(US Models)

(CE Models)

AV Control Systems

Summary of Contents for PAV6M-120

Page 1: ...ltage lighting do not remove factory installed bypass jumpers on load circuit terminals until load circuits are tested see start up procedure on page 6 The Pro AV DLC dimming modules are designed to o...

Page 2: ...or CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of total lighting load 10A for CE models Descr...

Page 3: ...s 2 Plan placement of modules Modules must be mounted vertically Make sure that nothing blocks the air channel between the back of the module and the wall Leave 6 152 mm of space above and below modul...

Page 4: ...es must have a load of at least 25W 40 W for CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of t...

Page 5: ...NTGRX 4B Scene Selection Control NTGRX 4M Master Control NTGRX 4PS Partition Control GRX CIR Infrared Ceiling Receiver GRX 4S DW ArchitraveTM Door Jamb Control GRX AV Interface Control EGRX 4S Europea...

Page 6: ...ermine the function of the unit s two buttons Scene 1 and Off Scene 9 Scene 10 Scene 13 Scene 14 Panic Control Fine Tuning Control Partition Status Zone Lockout Sequencing Scenes 5 16 Scenes 1 to 4 Sc...

Page 7: ...hting effects and make sure the Control Unit is working correctly To set up the PRO AV DLC Control Unit enter the setup mode and use the menu of setup codes that appear in the DISPLAY window Step by s...

Page 8: ...eased A capital letter indicates a button was pushed and a lowercase letter indicates a button was released The following is a list of how addresses are indicated Set up a Wallstation Control to talk...

Page 9: ...ed The response will be a ss followed by a string of eight ASCII characters one for each PAV control unit Each character represents the scene of each PAV control unit indicated by an A scene 11 will b...

Page 10: ...nput output RS232 DMX512 and other communication terminals of Wallstations must be supplied from a Listed Class 2 source The PRO AV DLC Control Unit Class 2 circuit is 12VDC EACH TERMINAL CAN ACCEPT U...

Page 11: ...n 68 75 mm deep minimum When mounting several units in a vertical layout one underneath the other allow at least 4 1 2 in 11 cm between units 3 Strip 1 2 in 12 mm insulation from 12 2 5 mm2 75 C coppe...

Page 12: ...ng relay that can handle the in rush current of ballasts The inter face gives PRO AV DLC Series Control Units the ability to both dim and switch electronic ballasts such as Lutron s Eco 10 TVE models...

Page 13: ...one from 800W VA to 1920W VA with the HP 2 3840W VA with the HP 4 5760W VA with the HP 6 Up to 28 800W VA by daisy chaining five HP 6 Modules HP 2 4 6 Modules can also accept 277V input load power fee...

Page 14: ...urrent Check each zone output current add power boosters where necessary GRX 8IT GRX IT SCENE BUTTONS 1 4 OFF BUTTON MASTER RAISE LOWER Appendix F Infrared Transmitters Receivers Transmitters Receiver...

Page 15: ...Page 15...

Page 16: ...0657 All others 1 610 282 3800 Website address www lutron com E mail product lutron com Warranty Lutron warrants each new unit to be free from defects in materials and workmanship and to perform under...

Reviews: