Page 3
2''
(51 mm)
Class 2/PELV wiring must enter
through this knockout.
Bottom View
2.188''
(56 mm)
2''
(51 mm)
3''
(76 mm)
Right Side View
RS232 wiring must enter
through this knockout.
4.125''
(104 mm)
2.375''
(60 mm)
5.875”
(150 mm)
2.875''
(73 mm)
Mounting Dimensions
14.5''
(368 mm)
9.25''
(253 mm)
9.375''
(238 mm)
1. Choose an appropriate location.
Select a convenient location, such as an electrical closet AV
room or above a ceiling (non-plenum). Make sure location is
at least 6’ from sensitive AV equipment (and its wiring). Also,
make sure to locate module where its slight noise (relays
clicking and slight humming) is acceptable. Ensure ambient
temperatures are between 32 °F-104 °F (0 °C-40 °C). Module
must be mounted away from steam pipes, direct sunlight, or
other heat sources.
2. Plan placement of modules.
Modules must be mounted vertically. Make sure that nothing
blocks the air channel between the back of the module and the
wall.
■
Leave 6” (152 mm) of space above and below modules and
3” (76 mm) of space on either side of modules.
■
Leave 10” (204 mm) between the top of the module and the
ceiling, and 6” (152 mm) between the bottom of the module
and the floor.
■
Leave 6” (152 mm) of clearance in front of each module.
3. Mount modules (see below).
Using the mounting dimensions shown below, mark (while keeping the module vertical), then drill mounting holes.
Securely fasten the module to the wall. Top mounting holes are keyed to facilitate mounting.
Airspace Required
Front View
Top View
Air Channel
3''
(76 mm)
6'' (153 mm)
10'' (254 mm)
3''
(76 mm)
3''
(76 mm)
3''
(76 mm)
6'' (153 mm)
Step 1:
Installing PRO AV DLC Series Control Units
This section shows how to install the PRO AV DLC.
Mounting and Dimensions
Load wiring must enter through
these knockouts.