Page 3

  

  

  

  

  

   

  

  

  

   

  

2''

(51 mm)

Class 2/PELV wiring must enter
through this knockout.

Bottom View

2.188''

(56 mm)

2''

(51 mm)

3''

(76 mm)

Right Side View

RS232 wiring must enter
through this knockout.

4.125''

(104 mm)

2.375''

(60 mm)

5.875”

(150 mm)

2.875''

(73 mm)

Mounting Dimensions

14.5''

(368 mm)

9.25''

(253 mm)

9.375''

(238 mm)

1. Choose an appropriate location.

Select a convenient location, such as an electrical closet AV
room or above a ceiling (non-plenum). Make sure location is
at least 6’ from sensitive AV equipment (and its wiring). Also,
make sure to locate module where its slight noise (relays
clicking and slight humming) is acceptable. Ensure ambient
temperatures are between 32 °F-104 °F (0 °C-40 °C). Module
must be mounted away from steam pipes, direct sunlight, or
other heat sources.

2. Plan placement of modules.

Modules must be mounted vertically. Make sure that nothing
blocks the air channel between the back of the module and the
wall.

Leave 6” (152 mm) of space above and below modules and

3” (76 mm) of space on either side of modules.

Leave 10” (204 mm) between the top of the module and the

ceiling, and 6” (152 mm) between the bottom of the module
and the floor.

Leave 6” (152 mm) of clearance in front of each module.

3. Mount modules (see below).

Using the mounting dimensions shown below, mark (while keeping the module vertical), then drill mounting holes.
Securely fasten the module to the wall. Top mounting holes are keyed to facilitate mounting.

Airspace Required

Front View

Top View

Air Channel

3''

(76 mm)

6'' (153 mm)

10'' (254 mm)

3''

(76 mm)

3''

(76 mm)

3''

(76 mm)

6'' (153 mm)

Step 1:

Installing PRO AV DLC Series Control Units

This section shows how to install the PRO AV DLC.

Mounting and Dimensions

Load wiring must enter through
these knockouts.

Summary of Contents for PAV6M-120

Page 1: ...ltage lighting do not remove factory installed bypass jumpers on load circuit terminals until load circuits are tested see start up procedure on page 6 The Pro AV DLC dimming modules are designed to o...

Page 2: ...or CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of total lighting load 10A for CE models Descr...

Page 3: ...s 2 Plan placement of modules Modules must be mounted vertically Make sure that nothing blocks the air channel between the back of the module and the wall Leave 6 152 mm of space above and below modul...

Page 4: ...es must have a load of at least 25W 40 W for CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of t...

Page 5: ...NTGRX 4B Scene Selection Control NTGRX 4M Master Control NTGRX 4PS Partition Control GRX CIR Infrared Ceiling Receiver GRX 4S DW ArchitraveTM Door Jamb Control GRX AV Interface Control EGRX 4S Europea...

Page 6: ...ermine the function of the unit s two buttons Scene 1 and Off Scene 9 Scene 10 Scene 13 Scene 14 Panic Control Fine Tuning Control Partition Status Zone Lockout Sequencing Scenes 5 16 Scenes 1 to 4 Sc...

Page 7: ...hting effects and make sure the Control Unit is working correctly To set up the PRO AV DLC Control Unit enter the setup mode and use the menu of setup codes that appear in the DISPLAY window Step by s...

Page 8: ...eased A capital letter indicates a button was pushed and a lowercase letter indicates a button was released The following is a list of how addresses are indicated Set up a Wallstation Control to talk...

Page 9: ...ed The response will be a ss followed by a string of eight ASCII characters one for each PAV control unit Each character represents the scene of each PAV control unit indicated by an A scene 11 will b...

Page 10: ...nput output RS232 DMX512 and other communication terminals of Wallstations must be supplied from a Listed Class 2 source The PRO AV DLC Control Unit Class 2 circuit is 12VDC EACH TERMINAL CAN ACCEPT U...

Page 11: ...n 68 75 mm deep minimum When mounting several units in a vertical layout one underneath the other allow at least 4 1 2 in 11 cm between units 3 Strip 1 2 in 12 mm insulation from 12 2 5 mm2 75 C coppe...

Page 12: ...ng relay that can handle the in rush current of ballasts The inter face gives PRO AV DLC Series Control Units the ability to both dim and switch electronic ballasts such as Lutron s Eco 10 TVE models...

Page 13: ...one from 800W VA to 1920W VA with the HP 2 3840W VA with the HP 4 5760W VA with the HP 6 Up to 28 800W VA by daisy chaining five HP 6 Modules HP 2 4 6 Modules can also accept 277V input load power fee...

Page 14: ...urrent Check each zone output current add power boosters where necessary GRX 8IT GRX IT SCENE BUTTONS 1 4 OFF BUTTON MASTER RAISE LOWER Appendix F Infrared Transmitters Receivers Transmitters Receiver...

Page 15: ...Page 15...

Page 16: ...0657 All others 1 610 282 3800 Website address www lutron com E mail product lutron com Warranty Lutron warrants each new unit to be free from defects in materials and workmanship and to perform under...