background image

Page 8

NOTE:

DIP Switch 6 and 7 should be set “ON” if operating with external Control Systems such as Crestron or PANJA (AMX)

The setting of the DIP switches affect the interface control between PRO AV DLC Control Units and your PC or auxiliary A/V equipment. DIP switch options are
described below:

DIP Switch 1: Zone Lock Retain
DIP Switch 2: Scene Lock Retain
DIP Switch 3: Sequence Retain 

– In the event of a power outage, the RS232 Interface will retain which PAV6 control units were in ZONE LOCK, SCENE

LOCK and SEQUENCE, respectively. Upon returning power, Control Units that had been in Zone Lock, Scene Lock, or Sequencing will stay locked or
sequencing if the DIP switches are in the ON position, When these DIP switches are in the OFF position, this information will 

not

be restored upon power up.

These DIP switches do not affect Zone Lock, Scene Lock, or Sequencing set by a GRX-AV in 4Q mode.

DIP Switch 4: Sequence Type 

– Set the scene range that PAV-6M control units will sequence, using the Sequence command. In the OFF position, the

PAV-6 control units will sequence scenes 1 through 4, In the ON position, they will sequence scenes 5 through 16.

DIP Switch 6: Raw Feedback 

– In the ON position, the programming interface will report when a button has been pushed or released on a PAV-6 control

unit or low voltage Wallstation. This response varies depending on the type of unit, as listed below:

PRO AV Digital Lighting Controller 

(PAV-6M-120 and PAV-6S-120, PAV-6M-230 and PAV-6S-230)

Scene Selection Control 

(NTGRX-4S/4S-IR and EGRX-4S/4S-IR)

Architrave Door Jamb Control 

(GRX-4S-DW)

Infrared Ceiling Receiver 

(GRX-CIR)

A/V Interface Control 

(GRX-AV)

Infrared Wireless Remote Controls 

(GRX-It & GRX-8IT) The first parameter indicated the address of the Wallstation Control or Control Unit upon which

the button was pushed or released. A capital letter indicates a button was pushed, and a lowercase letter indicates a button was released. The following is a list
of how addresses are indicated.

Set up a Wallstation Control to “talk” to a “listening” Control Unit

In order for Wallstation to communicate with a Control Unit, each Wallstation must be individually configured to “talk.”

The communication link is now established. The Control Unit will “listen” when the user presses a button on the Wallstation. You can proceed to the next
Wallstation and set up its communications.
For more specific, step-by-step instructions about setting up communications for each type of PRO AV DLC Wallstation, please refer to the instructions included
with each Wallstation.

3.

Take the Wallstation out of setup mode.

Press and hold top Scene
and OFF button
for 3 seconds . . .

. . . LEDs stop cycling

1.

Enter setup mode.

. . . LEDs cycle—Wallstation is “talking”

Press and hold top Scene
and OFF button for
3 seconds . . .

2.

Make the Control Unit “listen.”

Press and hold LEFT button for 3 seconds

. . . LEDs flash in unison—
Control Unit is “listening”

Identifying the load type for each zone

Lutron ships PRO AV DLC Control Units with all zones set for incandescent/halogen (tungsten) lighting. If your project has non-incandescent loads, change all
non-incandescent zones to the correct load type, through GRX Liaison or AV Control System.

Step 7:

Setting up RS232 Communication

Description

The PAV is equipped with an integral RS232 and capable of programming through Lutron’s Liaison programming software.
This unit allows for up to eight PRO AV units to be interfaced with your personal computer or auxiliary audio/video equipment via RS232. The interface can be
used to execute Control Commands and allow for Status Monitoring. Complete programming is allowed through other RS232 devices. This programming
software includes an internal astronomical timeclock. The GRX-Liaison software can also be used to schedule events, make Sequences, and program additional
PAV6S.

DIP Switches on Interface Board

Summary of Contents for PAV6M-120

Page 1: ...ltage lighting do not remove factory installed bypass jumpers on load circuit terminals until load circuits are tested see start up procedure on page 6 The Pro AV DLC dimming modules are designed to o...

Page 2: ...or CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of total lighting load 10A for CE models Descr...

Page 3: ...s 2 Plan placement of modules Modules must be mounted vertically Make sure that nothing blocks the air channel between the back of the module and the wall Leave 6 152 mm of space above and below modul...

Page 4: ...es must have a load of at least 25W 40 W for CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of t...

Page 5: ...NTGRX 4B Scene Selection Control NTGRX 4M Master Control NTGRX 4PS Partition Control GRX CIR Infrared Ceiling Receiver GRX 4S DW ArchitraveTM Door Jamb Control GRX AV Interface Control EGRX 4S Europea...

Page 6: ...ermine the function of the unit s two buttons Scene 1 and Off Scene 9 Scene 10 Scene 13 Scene 14 Panic Control Fine Tuning Control Partition Status Zone Lockout Sequencing Scenes 5 16 Scenes 1 to 4 Sc...

Page 7: ...hting effects and make sure the Control Unit is working correctly To set up the PRO AV DLC Control Unit enter the setup mode and use the menu of setup codes that appear in the DISPLAY window Step by s...

Page 8: ...eased A capital letter indicates a button was pushed and a lowercase letter indicates a button was released The following is a list of how addresses are indicated Set up a Wallstation Control to talk...

Page 9: ...ed The response will be a ss followed by a string of eight ASCII characters one for each PAV control unit Each character represents the scene of each PAV control unit indicated by an A scene 11 will b...

Page 10: ...nput output RS232 DMX512 and other communication terminals of Wallstations must be supplied from a Listed Class 2 source The PRO AV DLC Control Unit Class 2 circuit is 12VDC EACH TERMINAL CAN ACCEPT U...

Page 11: ...n 68 75 mm deep minimum When mounting several units in a vertical layout one underneath the other allow at least 4 1 2 in 11 cm between units 3 Strip 1 2 in 12 mm insulation from 12 2 5 mm2 75 C coppe...

Page 12: ...ng relay that can handle the in rush current of ballasts The inter face gives PRO AV DLC Series Control Units the ability to both dim and switch electronic ballasts such as Lutron s Eco 10 TVE models...

Page 13: ...one from 800W VA to 1920W VA with the HP 2 3840W VA with the HP 4 5760W VA with the HP 6 Up to 28 800W VA by daisy chaining five HP 6 Modules HP 2 4 6 Modules can also accept 277V input load power fee...

Page 14: ...urrent Check each zone output current add power boosters where necessary GRX 8IT GRX IT SCENE BUTTONS 1 4 OFF BUTTON MASTER RAISE LOWER Appendix F Infrared Transmitters Receivers Transmitters Receiver...

Page 15: ...Page 15...

Page 16: ...0657 All others 1 610 282 3800 Website address www lutron com E mail product lutron com Warranty Lutron warrants each new unit to be free from defects in materials and workmanship and to perform under...

Reviews: