background image

3

3.

  Turn power OFF.  Wire each dimmer according 

to steps 3 and 4 in "Single Unit Installation".

4.

  Install controls in switchbox(es).  Use center 

mounting holes for fi rst unit, then use offset mounting 
holes as required for proper alignment.  Allow 

1/32

 

in (.79 mm) between controls for ease in attaching 
faceplates.

5.

  Just snap on multigang faceplate (or multiple 

single faceplates) and adjust up or down for snug 
fi t.  Multigang faceplates (with mounting frames and 
instructions) are available in a variety of colors and 
sizes to simplify and beautify your installation.

Multigang Installation--

Side Sections Removed (Derating Required)

In multigang installations several dimmers or controls 
are grouped horizontally in one ganging switchbox 
or in a series of connected switchboxes.  Multigang 
faceplates are available to simplify and improve the 
appearance of this installation.  A multigang mounting 
frame is provided with standard multigang faceplates 
which ensures proper alignment of dimmers, easy 
application of the faceplate, and a fl at surface for the 
installation.  Refer to instruction sheet (supplied with 
multigang faceplate) when using these components.

1.

  Derating is necessary when side sections are 

removed.  Use Derating Chart (Table B) to determine 
maximum wattage of lamps safely dimmed when 
side sections are removed.  Match the dimmer model 
number and the number of side sections removed to 
determine the maximum load that can be controlled.

Table B.  Derating Chart - Maximum Wattage

 

 

Control 

No Sides 

1 Side 

2 Sides

Model 

Size  Removed Removed Removed

N-600 

600 W 

600 W 

500 W

N-1000 

1000 W 

900 W 

700 W

N-1500 

1500 W 

1250 W 

1000 W

N-2000 

2000 W 

1800 W 

1500 W

2.

  Determine the number of switchboxes necessary 

by using the Switchbox Requirement Chart (Table C).  
When ganging any combination of small dimmers 
(N-600, N-1000) and large dimmers (N-1500, N-2000), 
place all small dimmers together at one end of the 
gang and all large dimmers at the other end of the 
gang.

3.

  Remove only inner side sections.  Using pliers, 

bend side sections as far as you can and then back 
to their  original positions.  Repeat several times 
until side sections break off.

Note:  

Do not remove outer side sections of the two 

dimmers which are on the ends of the gang.

4.

  Turn power OFF.  Wire each dimmer according 

to steps 3 and 4 in "Single Unit Installation". 
Grounds need to be common.

5.

  Install controls in switchbox(es).  Use center 

mounting holes.  (With large controls, you can 
use offset mounting holes as required for proper 
alignment).  Allow 

1/32

 in (.79 mm) between controls 

for ease in attaching faceplates.

6.

  Just snap on a multigang faceplate or multiple 

single faceplates (see "Faceplate Cutting" on next 
page) and adjust up or down for snug fi t. Multigang 
faceplates (with mounting frames and instructions) 
are available in a variety of colors and sizes to 
simplify and beautify your installation.

Table C.  Switchbox Requirement Chart

Side Sections Removed

Side section break-off points

Offset Mounting Holes

Center Mounting Holes

                                     Number of Small Controls
 

    0 1 2 3 4 5 6

 

Number of Switchboxes Required

 

 

0 1 2 3 4 5 6 

Number 

 

1 3 4 5 6 7 8

of 

 

Large 

 

3 5 6 7 8 9 10

Controls 

 

5 7 8 9 10 

11 

12

 

 4 

7  9  10 11 12 13 14

Reviews: