background image

SENSOR ADJUSTMENTS
Factory Settings

Adjusting the “Lights Not On” Level: LOS-WDT-R only

1. Ensure that the ambient light is at the desired level.
2. Place sensor in Test Mode: Press and release black pushbutton.
3. Set photo cell: Turn the blue knob full clockwise (lights on no matter how bright the natural light is), then about 30

degrees counterclockwise.

4. Check for Lights-Out: Move from underneath the sensor, and remain still until the lights turn off. Move around normally

to turn the light on.

5. Adjust to desired level: If lights turn on, adjust the blue knob another 30 degrees counterclockwise and repeat step 3

until the lights remain off.

Note:

Set blue knob to 100% to disable photo cell functionality and leave secondary dry contact closure output func-

tionality intact.

Note: Not all models have every knob.

Control Settings (Blue Knob): LOS-WDT-R only

0

1000

0

1000

0

1000

Minimum (low):
Lights will never come on, even though
room is occupied.

Maximum (high):
Photo cell has no effect on operation 
(factory setting).

Normal:
200 to 600 LUX is normal range.

Lighting
Control
system

Red (+20-24 V    )

Gray (control: occupancy & photo cell signal)

Black (common)

Yellow/White (NO)

Black/White (NC)

Blue/White (Relay Common)

Choose wire based on functionality:
• Yellow/White: NO (normally open)

Open: Unoccupied
Closed: Occupied

• Black/White: NC (normally closed)

Open: Occupied
Closed: Unoccupied

Cap off unused wire.

WIRING DIAGRAMS

Relay Model Option: LOS-WDT-R only

R

A

B

Timer Test Mode
Push and Release: 

8 sec. test timer
(resets to Normal 
after 1 hour)

Push and Hold (flash):

Normal timer

Red: Infrared 
75% default

Green: Ultrasonic 
50% default

Blue: Photo cell
(R model only)
100% default

1 2 3 4

1 2 3 4

3

Wire Lengths (feet)

# Sensors

1

2

3

1

2

1

# Aux. PPs

0

0

0

1

1

2

22 AWG

750

375

250

375

250

250

20 AWG

1200

600

400

600

400

400

18 AWG

2400

1200

800

1200

800

800

Mounting to Wall or Ceiling Tile:

Redrill wiring routing hole
and (2) mounting holes
using Mounting Bracket
as template. Route wires
through wall and mount-
ing bracket. Secure
mounting bracket to
wall/ceiling tile using mounting screws, nuts, and wash-
ers (included).

Mounting in Acoustic Ceiling Tile:

Twist threaded mounting post onto
Mounting Bracket. Drill through ceiling tile
with assembly. Secure with washer and
nut. Route wiring through Mounting
Bracket and connect to wire harness.
Snap bracket cover in place to
conceal wiring and bracket. 

Off (Default)

On

Automatic (Normal)

Manual lights on (Override)

Not used

Not used

LED on (Normal)

LED off

Retain Settings (Normal)

Any change resets learned settings

Off

On

OFF

8

OFF

4

ON

15

ON

30

OFF

min.

ON

min.

OFF

min.

ON

min.

Auto Timer Adjust On

Auto Timer Adjust Off

Auto Sensitivity Adjust On

Auto Sensitivity Adjust Off   

SENSOR ADJUSTMENTS

Override Settings

Mounting Plate Dimensions

Measurements are in inches (mm)

2.25
(58)

3.35
(86)

2.5 (63)

.52 (13.3)

1 2 3 4

1 2 3 4

A

B

}

}

}

PRE-INSTALLATION

1. For installation by a qualified electrician in accordance with national and local codes and the following instructions.
2. For indoor use only.
3.

CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing. Never wire energized electrical
components.

4.

CAUTION: USE COPPER CONDUCTORS ONLY.

5.

CAUTION: Do not connect this Class 2/PELV product to line voltage/mains cable.

6. Check to see that the device type and rating is suitable for the application.
7. Do not install if product or lens have any visible damage.
8. If moisture or condensation is evident, allow the product to dry completely before installation.

INSTALLATION AND MOUNTING

}

2

Either Method:

Feed wiring harness through the back of the sensor body and out the exit slot. Snap sensor
onto mounting post. Plug wiring harness into connector on the left side (opposite exit slot)
and place wiring under wire tabs. Align sensor and tighten position locking screw.

R

Gray wire: logic with photo cell active:

Room First Occupied              

During Occupancy

Light level:

Lights:

Light level:

Lights:

Below set value

Turn on

Falls below set value

Turn on

Above set value

Remain off

Moves above set value

Remain on

ON

ON

Blue: Cap off

Reviews: