Lutron Electronics LOS-W Series Installation Instructions Manual Download Page 3

®

Sensor Adjustments

Factory Settings

Adjusting the “Lights Not On” Level: -R models only

1. Ensure that the ambient light is at the desired level.
2. Place sensor in Test Mode: Push and release Timer Test Mode button.
3. Set photo cell: Turn the blue knob full clockwise (lights on no matter how bright the natural light is), then about 
 30˚ 

counterclockwise.

4. Check for Lights-Out: Move from underneath the sensor, and remain still until the lights turn off. Move around 

normally to turn the light on.

5. Adjust to desired level: If lights turn on, adjust the blue knob another 30˚ counterclockwise and repeat step 3 

until the lights remain off.

 

Note:

 Set blue knob to 100% to disable photo cell functionality and leave secondary dry contact closure 

output functionality intact.

Note:

 Not all models have every knob.

Control Settings (Blue Knob): -R models only

0

1000

0

1000

0

1000

Minimum (low):
Lights will never come on, even though 
room is occupied.

Maximum (high):
Photo cell has no effect on operation 
(factory setting).

Normal:
200 lx to 600 lx is normal range.

Lighting 
Control 
system

Red (+20-24 V

)

Gray (control: occupancy & photo cell signal)

Black (common)

Yellow/White (NO)

Black/White (NC)

Choose wire based on functionality:
• Yellow/White: NO (normally open)
   Open: Unoccupied
   Closed: Occupied
• Black/White: NC (normally closed)
   Open: Occupied
   Closed: Unoccupied
Cap off unused wire.

Wiring Diagrams

Relay Model Option: -R models only

1

2

3

4

1

2

3

4

Red: Infrared 
75% default

Green: Ultrasonic 
50% default

Blue: Photo cell 
(-R models only)
100% default

Blue: Cap off

Blue/White (Relay Common)

Timer Test Mode
Push and Release: - 8 second test timer (resets to Normal after 1 hour)
Push and Hold (flash): - Normal timer

    Gray wire: logic with photo cell active: 

Room First Occupied

Light Level

Lights

Below set value

Turn on

Above set value

Remain off

During Occupancy

Light Level

Lights

Falls below set value

Turn on

Moves above set value

Remain on 

Relay Output

Summary of Contents for LOS-W Series

Page 1: ...ent The occupant sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves indirect hanging fixtures etc For WIR models do not place sensor within 4 ft 1 2 m...

Page 2: ...esets learned settings Off Default On OFF 8 minutes OFF 4 minutes ON 15 minutes ON 30 minutes OFF ON OFF ON Auto Timer Adjust On Auto Timer Adjust Off Auto Senstivity Adjust On Auto Sensitivity Adjust...

Page 3: ...1000 0 1000 Minimum low Lights will never come on even though room is occupied Maximum high Photo cell has no effect on operation factory setting Normal 200 lx to 600 lx is normal range Lighting Contr...

Page 4: ...r consequential damages so the above limitation or exclusion may not apply to you Lutron and are registered trademarks of Lutron Electronics Co Inc 2013 World Headquarters Lutron Electronics Co Inc 72...

Page 5: ...de luz indirecta etc Para modelos WIR no coloque el sensor dentro de 1 2 m 4 pies de orificios de aire manejadoras de aire ventanas ventiladores etc ya que podr a causar falsos disparos Para modelos W...

Page 6: ...00 pies 800 pies 800 pies Largos del Cable cuando se alimenta con paquete de alimentaci n ON OFF ON OFF Montaje en la Pared o el Cielorraso Taladre el orificio de conducci n del cableado y los 2 orifi...

Page 7: ...mo bajo Las luces no se encender n a n si la habitaci n est ocupada M ximo alto La fotocelda no tiene efecto en la operaci n configuraci n de f brica Normal 200 lx a 600 lx es el rango normal Sistema...

Page 8: ...un cableado o una instalaci n incor rectos Esta garant a no cubre da os incidentales o indirectos La responsabilidad de Lutron ante una demanda por da os causados por o relacionados con la fabricaci...

Reviews: