Sensor Adjustments
Factory Settings
Adjusting the “Lights Not On” Level: -R models only
1. Ensure that the ambient light is at the desired level.
2. Place sensor in Test Mode: Push and release Timer Test Mode button.
3. Set photo cell: Turn the blue knob full clockwise (lights on no matter how bright the natural light is), then about
30˚
counterclockwise.
4. Check for Lights-Out: Move from underneath the sensor, and remain still until the lights turn off. Move around
normally to turn the light on.
5. Adjust to desired level: If lights turn on, adjust the blue knob another 30˚ counterclockwise and repeat step 3
until the lights remain off.
Note:
Set blue knob to 100% to disable photo cell functionality and leave secondary dry contact closure
output functionality intact.
Note:
Not all models have every knob.
Control Settings (Blue Knob): -R models only
0
1000
0
1000
0
1000
Minimum (low):
Lights will never come on, even though
room is occupied.
Maximum (high):
Photo cell has no effect on operation
(factory setting).
Normal:
200 lx to 600 lx is normal range.
Lighting
Control
system
Red (+20-24 V
)
Gray (control: occupancy & photo cell signal)
Black (common)
Yellow/White (NO)
Black/White (NC)
Choose wire based on functionality:
• Yellow/White: NO (normally open)
Open: Unoccupied
Closed: Occupied
• Black/White: NC (normally closed)
Open: Occupied
Closed: Unoccupied
Cap off unused wire.
Wiring Diagrams
Relay Model Option: -R models only
1
2
3
4
1
2
3
4
Red: Infrared
75% default
Green: Ultrasonic
50% default
Blue: Photo cell
(-R models only)
100% default
Blue: Cap off
Blue/White (Relay Common)
Timer Test Mode
Push and Release: - 8 second test timer (resets to Normal after 1 hour)
Push and Hold (flash): - Normal timer
Gray wire: logic with photo cell active:
Room First Occupied
Light Level
Lights
Below set value
Turn on
Above set value
Remain off
During Occupancy
Light Level
Lights
Falls below set value
Turn on
Moves above set value
Remain on
Relay Output