Lutron Electronics LOS-W Series Installation Instructions Manual Download Page 1

®

Occupancy Sensor
LOS-W Series
Installation Instructions 

(U)LOS-WIR
(U)LOS-WDT
(U)LOS-WDT-R
IEC PELV/NEC

R

 Class 2 Devices

English

Range Diagram and Dimensions

US 

Minor 

Motion

IR Minor Motion

IR Major Motion

US 

Major 

Motion

US Major Motion

US Minor Motion

Description

The LOS-W Series of wall-mounted sensors incorporate infrared (WIR) and dual technologies (WDT) - 
ultrasonic and infrared. They are used in spaces with pendant fixtures, ceiling fans, or high ceilings. They 
integrate into Lutron

R

 systems or function as stand-alone controls using a Lutron

R

 power pack.

Features

•  Intelligent, continually adapting sensors
•  20 to 24 V

-

IEC PELV / NEC

R

 Class 2

, 33 mA nominal

• 1600 ft

2

 (150 m

2

) coverage

•  Flexible mounting on wall or ceiling
•  Second dry contact closure output available on -R models
•  LED indicators: Ultrasonic (US)-green, Infrared (IR)-red
•  For indoor use only

Coverage and Placement

•  The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, 

shelves, indirect hanging fixtures, etc.

•  For -WIR models, do not place sensor within 4 ft (1.2 m) of air vents, air handlers, windows, fans, etc., as this 

may cause false triggering.

•  For -WDT and -WDT-R models, do not place sensor within 6 ft (1.2 m) of air vents, air handlers, windows, 

fans, etc., as this may cause false triggering.

•  Place the sensor on the same wall as the doorway so that hallway traffic will not affect the sensor.
•  Closely follow the diagrams for major and minor motion coverage.
•  Decrease total coverage area by 15% for “soft” rooms (e.g. heavy draperies or heavy carpeting).
•  Indicated coverage is when sensor is mounted at 8 ft (2.4 m) high.

Model

US Minor Motion

US Major Motion

IR Minor 
Motion

IR Major 
Motion

WIR

NA

NA

20 ft (6.1 m)

40 ft (12.2m)

WDT

23 ft x 23 ft (7.0 m x 7.0 m)

32 ft x 32 ft (9.8 m x 9.8 m)

20 ft (6.1 m)

40 ft (12.2 m)

WDT-R

23 ft x 23 ft (7.0 m x 7.0 m)

32 ft x 32 ft (9.8 m x 9.8 m)

20 ft (6.1 m)

40 ft (12.2 m)

P/N 031259 Rev C 03/13

US - 

Ultrasonic

IR - 

Infrared

Summary of Contents for LOS-W Series

Page 1: ...ent The occupant sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves indirect hanging fixtures etc For WIR models do not place sensor within 4 ft 1 2 m...

Page 2: ...esets learned settings Off Default On OFF 8 minutes OFF 4 minutes ON 15 minutes ON 30 minutes OFF ON OFF ON Auto Timer Adjust On Auto Timer Adjust Off Auto Senstivity Adjust On Auto Sensitivity Adjust...

Page 3: ...1000 0 1000 Minimum low Lights will never come on even though room is occupied Maximum high Photo cell has no effect on operation factory setting Normal 200 lx to 600 lx is normal range Lighting Contr...

Page 4: ...r consequential damages so the above limitation or exclusion may not apply to you Lutron and are registered trademarks of Lutron Electronics Co Inc 2013 World Headquarters Lutron Electronics Co Inc 72...

Page 5: ...de luz indirecta etc Para modelos WIR no coloque el sensor dentro de 1 2 m 4 pies de orificios de aire manejadoras de aire ventanas ventiladores etc ya que podr a causar falsos disparos Para modelos W...

Page 6: ...00 pies 800 pies 800 pies Largos del Cable cuando se alimenta con paquete de alimentaci n ON OFF ON OFF Montaje en la Pared o el Cielorraso Taladre el orificio de conducci n del cableado y los 2 orifi...

Page 7: ...mo bajo Las luces no se encender n a n si la habitaci n est ocupada M ximo alto La fotocelda no tiene efecto en la operaci n configuraci n de f brica Normal 200 lx a 600 lx es el rango normal Sistema...

Page 8: ...un cableado o una instalaci n incor rectos Esta garant a no cubre da os incidentales o indirectos La responsabilidad de Lutron ante una demanda por da os causados por o relacionados con la fabricaci...

Reviews: