background image

®

Job Name:

Job Number:

Model Numbers:

Page

S P E C I F I C AT I O N   S U B M I T TA L

LOS-CUS   4

09.04.08

Occupant Sensors

LOS-CUS Series

Sensors

Neutral

Power
Pack

Manual

switch off

(optional)

Lighting
Load

Note: Maximum 3 occupant sensors.

Red (+20 - 24 V

)

Blue (signal)

Black
(common)

Black

White

Red
Red

1 to 3 Sensors with Power Pack

Switching Multiple Loads with Auxiliary Power Packs

Hot

Neutral

Hot

Manual switch off (optional)

Lighting

Load

Lighting
Load

Power
Pack

Auxiliary
Power
Pack

Red

Red

Red (+20 - 24 V

)

Blue (signal)

Black
(common)

Note: Maximum of 3 devices total 

(occupant sensors and auxiliary power packs)

can be connected to a power pack.

Black

White

Red
Red

120 / 277 / 347 V

60 Hz;

230 V

50 / 60 Hz

120 / 277 /

347 V

60 Hz;

230 V
50 / 60 Hz

Wiring: Stand-Alone Control

4

Summary of Contents for LOS-CUS-500-WH

Page 1: ...2 4 to 3 7 m ceiling Affords choice of turning lights off or dimming to a preset level in the unoccupied state when integrated with a Lutron system Models Available C Ca at t N No o C Co ollo or r C C...

Page 2: ...nic motion detected Housing Rugged high impact injection molded plastic Color coded leads 6 in 15 cm Power Operating voltage 20 24 V PELV Class 2 USA low voltage Operating current 33 mA nominal Contro...

Page 3: ...ting controller Note Power pack may be required when interfaced to lighting control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoS...

Page 4: ...ed Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliary Power Pack Red Red...

Page 5: ...80 occupant sensor 500 and 1000 models place the sensor on the same wall as the doorway so that traffic in a hallway will not affect the sensor otherwise place in center of room Closely follow the dia...

Page 6: ...n n S St ta an nd da ar rd d C Ce eiilliin ng g o or r F Fiix xt tu ur re e Mount twist lock cover plate using mounting screws nuts and washers included Drill punch wire routing hole through ceiling t...

Page 7: ...Compensation No Normal Yes Use increased turn on threshold Adjust Timer Automatically Use Manual Setting No adjustment Adjust Sensitivity Automatically Adjust Sensitivity Manually 1 Remove the retaine...

Reviews: