background image

®

Job Name:

Job Number:

Model Numbers:

Page

S P E C I F I C AT I O N   S U B M I T TA L

LOS-CUS   1

09.04.08

Occupant Sensors

LOS-CUS Series

Sensors

Ultrasonic Ceiling Mount Sensor

The LOS-CUS Series ceiling-mount ultrasonic sensors can
integrate into Lutron systems or function as stand-alone
controls using a Lutron power pack. Any movement within
the sensor’s range causes a shift in the original emitted
frequency. The sensor’s receiver identifies any change in
frequency as motion and either turns the lights on or
maintains lights on.

Features

• Intelligent, continually adapting ultrasonic sensor
• Snap-locks to ceiling-mounted cover plate
• Excellent minor motion sensitivity
• Non-Volatile Memory: settings saved in protected 

memory are not lost during power outages

• 500 to 2000 sq.ft. (46 to 186 m

2

) coverage when

mounted on an 8 - 12 ft. (2.4 to 3.7 m) ceiling

• Affords choice of turning lights off or dimming to a preset 

level in the unoccupied state when integrated with a 
Lutron system.

Models Available

C

Ca

att..  N

No

o..

C

Co

ollo

orr

C

Co

ov

ve

erra

ag

ge

e

F

Fiie

elld

d  o

off  V

Viie

ew

w

LOS-CUS-500-WH

White

500 sq.ft. (46 m

2

)

180°

LOS-CUS-1000-WH

White

1000 sq.ft. (93 m

2

)

180°

LOS-CUS-2000-WH

White

2000 sq.ft. (186 m

2

)

360°

Self-Adaptive Feature

Designed to meet the challenges found in a wide variety of spaces, the LOS-CUS Series provides reliable
detection with high minor motion detection. The intelligent, continually adapting sensor technology
eliminates manual sensitivity and timer adjustments during installation and over the life of the product. The
internal microprocessor analyzes the information from the ultrasonic technology and determines the optimum
setting to use in order to properly cover the space. Should the room be reconfigured (e.g., new furniture),
the software will adapt to continue to provide correct time out for the lights.

1

Summary of Contents for LOS-CUS-500-WH

Page 1: ...2 4 to 3 7 m ceiling Affords choice of turning lights off or dimming to a preset level in the unoccupied state when integrated with a Lutron system Models Available C Ca at t N No o C Co ollo or r C C...

Page 2: ...nic motion detected Housing Rugged high impact injection molded plastic Color coded leads 6 in 15 cm Power Operating voltage 20 24 V PELV Class 2 USA low voltage Operating current 33 mA nominal Contro...

Page 3: ...ting controller Note Power pack may be required when interfaced to lighting control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoS...

Page 4: ...ed Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliary Power Pack Red Red...

Page 5: ...80 occupant sensor 500 and 1000 models place the sensor on the same wall as the doorway so that traffic in a hallway will not affect the sensor otherwise place in center of room Closely follow the dia...

Page 6: ...n n S St ta an nd da ar rd d C Ce eiilliin ng g o or r F Fiix xt tu ur re e Mount twist lock cover plate using mounting screws nuts and washers included Drill punch wire routing hole through ceiling t...

Page 7: ...Compensation No Normal Yes Use increased turn on threshold Adjust Timer Automatically Use Manual Setting No adjustment Adjust Sensitivity Automatically Adjust Sensitivity Manually 1 Remove the retaine...

Reviews: