STEP 7 (continued)
Configuring the Emergency
Setting Levels
A.
From the
Main Menu
use and to
highlight
Panel Setup
and
press or (OK).
B.
Use and to
highlight
Emergency Setup
and
press or (OK).
C.
When asked if the panel has emergency
functionality,
use and to
select
Yes
and press
or (Next).
D.
The Emergency Setup screen lists all the circuits
and their default emergency settings. Use
and
to select a circuit and
and
to change the
setting for that circuit. To simultaneously change all
circuits, select
All Circuits
and
use and to
change the setting.
Note:
The
All Circuits
function enables you to
simultaneously adjust the percentage for all
dimming circuits or to turn all circuits off and on.
Circuit settings depend on the circuit type:
Switching:
ON, OFF, --- (unaffected)
Dimming:
OFF, 1 - 100%, --- (unaffected)
Motors:
Open, Close, Stop, Jog Up, Jog Down
Fans:
Low, Medium, Medium-High, High
Note:
The
--- (unaffected)
setting means the
circuit is not affected by emergency mode.
When the circuits are programmed for emergency
mode,
press or (Next).
E.
The Select CCO Address screen is displayed only if
control station devices with contact closure outputs
(OMX-AV or OMX-CCO-8) have been entered into
the system. Use
and
to scroll through the list
to select the output to be associated with the
button being programmed. Use
and
to
change the setting for that output between:
maintained open
,
momentary open
,
momentary
close
,
maintained close
or
---
(unaffected). When
the outputs are programmed press
or
(Done)
to update the database.
F.
For multi-panel systems, repeat the procedure to
program the emergency settings at each remote
panel.
OK
OK
OK
OK
OK
Emergency Setup
All Circuits
- 100%
001
Dim
- 100%
002
Dim
- 100%
003
Relay
- O N
Previous
Next
Panel Setup
Panel Addressing
Emergency Setup
Afterhours Setup
Back
OK
B.
D.
Select CCO Address
A01 CCO1 - Maintained Open
A01 CCO2 - ---
A01 CCO3 - ---
A01 CCO4 - ---
Previous
Done
E.
Load Setup
Emergency Setup
have emergency
Yes
Cancel
Next
C.
Does this panel
Address
number
Contact closure
output number