G7000P
Class 2 Terminal Operation and Bus Supply Programming
Contact Closure Inputs
•
Contact closures on the Bus Supply may be used for integrating a BMS system
or occupancy sensors with relay outputs to an EcoSystem Lighting Network
•
CCI-1 and CCI-2 are programmable to control two different groups of ballasts (one group per CCI).
CCIs force the assigned groups to an “Occupied mode” or “Unoccupied mode”
•
Occupied mode enables the system to operate normally: wallstations, daylight
sensors, occupancy sensors, and infrared transmitters control ballasts as programmed
•
Unoccupied mode turns EcoSystem ballasts and BMFs off. The off setting is overridden by an
occupancy sensor, or the contact closure input. Unoccupied mode is locally overridden if an occupancy
sensor in the space detects motion. Once the local sensor times out, the space becomes unoccupied.
•
Each input may be normally open (NO) or normally closed (NC) (see below for required OPT switch settings)
OPT SWITCH FUNCTION
GRAFIK 7000™ Master
Processor/eLumen Manager
seeTouch
TM
Digital Bus
Supply
(CS-1L-CM)
EcoSystem Sensors
and Controls
EcoSystem Ballasts
or BMFs
Contact Closure
Interfaces
Digital Bus
Supply
OPT
Description
Mode
1
CCI-1
OFF = Normally closed
Input type
ON = Normally open
2
CCI-2
OFF = Normally closed
Input type
ON = Normally open
3
Reserved
4
Reserved
5
Emergency
OFF = Ignore input
Operation
ON = Input Valid (open = emerg)
6
Programmer
OFF = Programmer enable
Lockout
ON = Programmer disable
OPT 7 OPT 8
Function
OFF
OFF
Normal Operation (default)
OFF
ON
Override: High End
ON
OFF
Override: Low End
ON
ON
Override: Off
OPT SWITCHES 7 AND 8
24
|
Lutron
www.lutron.com/ecosystem Lutron World Headquarters:
1.610.282.3800
To other
OMX devices
EcoSystem
™
|
GRAFIK 7000
™
system