Luna LSM Series Maintenance And User Manual Download Page 24

24

FK.102 (Rev.02) 08.10.2018

AB UYGUNLUK BEYANI

EU DECLARATION OF CONFORMITY

 ( No 0002 )

Cihaz modeli/Cihaz

: LSM40

Instrument model/Instrument 

Sayacın seri numarası: 

Serial number of the meter:

Üretici adı ve adresi

Name and address of the manufacturer 

: LUNA A.S.

  10.001 Str. No:9

  Ataturk O.S.B.

  Cigli-Izmir-TURKEY

Bu uygunluk beyanı üreticinin sorumluluğu altında verilir.

This declaration of conformity is issued under the sole responsibility of the manufacturer.

Beyanın konusu:

Object of declaration:

5.

Yukarıda belirtilmiş olan uygunluk beyanı 

aşağıdaki ilgili AB uyumlandırma mevzu

-

atı ile uyumludur:

The  object  of  the  declaration  described 

above is in conformity with the relevant 

Union harmonisation legislation:

-Üye  devletlerin  ölçü  aletleri  pazarındaki 

uyumluluğu  gerçekleştirmek  üzere  ya-

salarının  uyumluluğu  hakkındaki  Avrupa 

Parlamentosu  ve  Konseyi’nin  2014/32/EU 

direktifi

-WELMEC Kılavuzu 11.1, Sayı 4

-WELMEC Kılavuzu 7.2, Sayı 5

-OIML R 46 -1/-2 Sürüm 2012 (E)

-Direktif  2015/13/EU

-Directive 2014/32/EU of the European Par-

liament and of the Council of 26 February 

2014  on  the  harmonisation  of  the  laws  of 

the  member  states  relating  to  the  making 

available  on  the  market  of  measuring  ins-

truments.

-Welmec Guide 11.1, Issue 4

-Welmec Guide 7.2, Issue 5

-OIML R 46 -1/-2 Edition 2012 (E)

-Directive 2015/13/EU

Uyumluluğun beyan edildiği ilgili standart referansları:

References to the relevant harmonised standards to which conformity is declared:

İlgili MODÜL B ve MODÜL D uygunluk değerlendirme prosedürle

-

rini gerçekleştiren ve yayınlayan 1432 sayılı onaylanmış kuruluş 

(Slovenska legalna metrologia n.o.)

The notified body No. 1432 (Slovenska legalna metrologia n.o.) performed conformity as-

sessment procedures MODULE B and MODULE D and issued:

4.

3.

2.

1.

6.

7.

AB Tip Onayı Belge No

: SK15-064 MI-003

EC type-approval certificate No

Kalite Yönetim Sistemi Onay No

: SK-09-015D

Approval on a Quality Management System No

Firma adına imza:

8.

Signed for and on behalf of:

Izmir, 

Mustafa KARABAGLI

Yönetim Kurulu Başkanı

(Chairman of the Board)

Tarih:

Date

Summary of Contents for LSM Series

Page 1: ...IMPORT EXPORT ACTIVE REACTIVE SINGLE PHASE ELECTRONIC ELECTRICITY METERS MAINTENANCE AND USER S MANUAL LSM40 LSM SERIES KK_EN_LSM40_19 02...

Page 2: ...Str No 9 Atat rk O S B 35620 i li zmir T RK YE Tel 90 232 472 15 45 Fax 90 232 472 15 50 www lunatr com SERVICES Main Technical Service LUNA ELEKTR K ELEKTRON K SAN VE T C A 10001 Str No 9 Atat rk O...

Page 3: ...eatures in user s manual of LUNA Electronic Electricity Meters usage out of range set in the manual are not considered under cover of warranty LSM Series Active Reactive Multi Tariff Single Phase Elec...

Page 4: ...the electricity distri bution company must be complied Humidity direct exposure to sunlight rain and cold should be avoided As electricity measurement are performed using electronic com ponents to avo...

Page 5: ...rom 2 8 0 to 2 8 4 export in the format 000000 000 kWh 1 8 0 and 2 8 0 gives the total tariff T information and 1 8 1 1 8 4 and 2 8 1 2 8 4 gives T1 T2 T3 T4 information of import energy and export en...

Page 6: ...s process is done automatically at the end of month if the maximum demand is not reset manually within that month LSM series meters stores the maximum demand and date and time of the maximum demand fo...

Page 7: ...The meter keeps logs of the following information in its non volatile memory 1 9 1 Phase Interruptions The start and end time of phase interruptions are stored in the non vo latile memory of the mete...

Page 8: ...n in this case unless the menu button is pressed and auto scrolling is off 1 9 7 Magnetic Interventions The last 10 intervals when magnetic field is applied and the number of magnetic interventions ar...

Page 9: ...he poly phase meter is unbalanced with respect to the average current of all phases 1 at least one of the phase voltages in the poly phase meter is unbalanced with respect to the average voltage of al...

Page 10: ...read with the LSM meter reading software using the Status tab After reading the statuses the bits which are set ap pear in bold on the left with their meanings Note that some of the status bits may n...

Page 11: ...oad profile data is erased If export feature is enabled import and export consumptions are recorded however if export feature is disabled only the import consumption is recorded which significantly in...

Page 12: ...connected if the feature is enabled If the Consumption Limitation Repeat 96 74 24 feature is enabled value 1 the electricity can be reconnected for Allowed Button Connect Count 96 73 33 times by pushi...

Page 13: ...related to over and under voltage events that can be changed are as follows val_ov 96 73 20 The value of voltage over which over voltage is detected val_uv 96 73 21 The value of voltage below which u...

Page 14: ...cannot reconnect the lr until the end of the month if this feature is enabled 1 10 16 Auto Disconnect LR on Over Current Consumption Limitation LSM Series meters can optionally support disconnecting...

Page 15: ...YY MM DD hh mm A1 000000 OBIS code with data format where A is the password level 0 1 2 The complete writing logs can be read by asking the meter 96 92 X 00 OBIS code starting with X as 1 and incremen...

Page 16: ...erations resets demand With this button the past month information about invoice periods can be gi ven Example 1 8 1 1 The OBIS value indicates the T1 consumption rate for the previous invoice period...

Page 17: ...ve Reactive Model Each light pulse indicates 1 VArh reactive power consumption 2 5 Optical Port Optical port feature enables data transfer and programming in comp liance with EN 61107 communication pr...

Page 18: ...on 2 Option 3 5 MENUS 5 1 Main Menu When the device is connected to energy the list indicating Total Im port Active Energy menu will appear in terms of kWh on the LCD scre en At 5 second intervals T1...

Page 19: ...The menu is as records of the export energy used at the specified time in terval EXPORT T3 TARIFF The menu is as records of the export energy used at the specified time in terval EXPORT T4 TARIFF Menu...

Page 20: ...case of unauthorized exe cution of this process warranty will be invalid and penalty fees may be incurred MAIN COVER REMOVAL NOTIFICATION It indicates that main cover is opened In case of unautho rize...

Page 21: ...he menu but ton of the meter for 4 seconds In the sub menu Voltage Current Power Factor Frequency information and previous month information of T T1 T2 T3 T4 Reactive inductive Reactive Capacitive Dem...

Page 22: ...umed energy T4 ta riff in previous month menu T4 blinks Total consumed energy Reacti ve Inductive in previous month menu Total consumed energy Reacti ve Capacitive in previous month menu Total demand...

Page 23: ...SCHEME 7 CONNECTIONS FK 104 Rev 01 19 10 2018 6 SPHYSICAL DIMENSIONS OF THE METER Phase R Phase S Phase T Neutral LOAD LCD SCREEN MENU BUTTON OPTICAL PORR Demand Reset Button Optional Seal of Distribu...

Page 24: ...vuzu 7 2 Say 5 OIML R 46 1 2 S r m 2012 E Direktif 2015 13 EU Directive 2014 32 EU of the European Par liament and of the Council of 26 February 2014 on the harmonisation of the laws of the member sta...

Page 25: ...warranty cert f cate Customer Product Brand Type Model Name Name Address Address Tel Fax Tel Fax e mail Invoice Date Number e mail Serial Number LUNA APPROVAL Stamp Signature Electronic Electricity M...

Page 26: ...ustrial product with similar features to the consumer until the completion of repair of the product 7 Failures resulting from the use contrary to the matters located in the user manual for the product...

Page 27: ...ng Temperature Range T1 Tariff T2 Tariff T3 Tariff Daylight Saving Time Battery Life Weight LSM40 3 x 230 400VAC 20 Un 15 Un 5 100 A 1000 imp kWh 20mA 50 Hz 2 Directly connected to primary active reac...

Page 28: ...ELECTRONIC ELECTRICITY METERS SMART GRID SYSTEMS Phone 90 232 472 15 45 Fax 90 232 472 15 50 info lunatr com www lunatr com...

Reviews: