10
1: RS485 communication is supported
1: RF communication is supported
1: PLC communication is supported
1: Plug&Play communication module is sup-
ported
1: Latching Relay is supported
1: EEPROM is supported
1: SPI flash is supported
1: Software upgrade is not supported
1: Export energy measurement feature is
enabled
1: Reactive energy measurement is supported
1: Load Profile recording is supported
1: reserved
1: LCD backlight is supported
1: Advanced phase interruptions feature is
supported.
1: Holiday tariff feature is supported
1: LCD sub-menu is supported
1: Advanced log feature is supported
1: DLMS communication is supported
1: If 1, 10000 impulse mode; if 0, 1000 impulse
mode
1: reserved
1: reserved
1: reserved
1: reserved
1: reserved
1: Over and under voltage detection are sup-
ported
1: Over current detection is supported
1: Magnetic tamper detection is supported
1: Daylight saving time feature is enabled
1: reserved
1: reserved
1: reserved
1: reserved
The statuses can also be easily read with the LSM meter reading software
using the Status tab. After reading the statuses, the bits which are set ap-
pear in bold on the left with their meanings.
Note that, some of the status
bits may not be available in all meter models.
1.9.10. Meter Logs
Meter keeps logs of various errors and events in its non-volatile me-
mory. These logs can be read using 96.75*1(00),..., 96.75*150(00)
OBIS codes. The log data is in (YY-MM-DD,hh:mm:ss |<error code>)
format.
The complete logs can be read by asking the meter 96.75*X(00) OBIS
code starting with X as 1, and incrementing X until an empty log data
(--------,--:--:--|--) is received or X reaches 150. The basic error codes
are as follows:
01: Current energy consumption values inconsistent
02: Extreme energy consumption value measured
06: Meter is initialized
07: Hard reset occured
08: Soft reset occured
12: EEPROM write error
16: Meter is programmed
19: RF module malfunctioned
20: PLC module malfunctioned
24: Battery 1 level dropped to critical level
25: Battery 2 level droped to critical level
33: Error reading time backup
35: Load profile structure error
38: RTC module malfunctioned
40: Flash memory write error
50: Meter firmware upgraded
FK.104 (Rev.01) 19.10.2018