23
EN
Additional errors:
- from automatic compensation reference junction temperature
2
C
- from automatic resistance compensation of resistance thermometer
wires
0.3
C
Current flowing through resistance thermometer sensor:
0.22 mA
Measurement time
: 0.25 s
Input resistance:
for voltage input: 100 k
; for current input:10
Error detection in the measurement circuit:
- thermocouple, Pt100, Pt1000 measuring range exceeded
- 0
10 V over 11 V
- 0
5 V over 5.5 V
- 0
20 mA over 22 mA
- 4
20 mA over 1 mA and over 22 mA
Input 3 (depends on input 3 in ordering code)
Sensor type
Range
Intrinsic error
linear current
0...20 mA
0.2% ± 1 digit
linear current
4...20 mA
0.2% ± 1 digit
linear voltage
0...5 V
0.2% ± 1 digit
linear voltage
0...10 V
0.2% ± 1 digit
potentiometric 100
0...100
0.2% ± 1 digit
potentiometric 1000
0...1000
0.2% ± 1 digit
Measurement time
: 0.25 s
Input resistance:
for voltage input 100 k
; for current input 50
Setting range of controller parameters:
see Table 1 (see full version
of service manual, available at www.lumel.com.pl)
Binary inputs 1…3
voltageless: shorting resistance
10 k
;
opening out resistance
100 k
Output 1 and 2 types:
- relay voltageless: NOC contact, load capacity
2 A/230 VAC
- voltage transistor 0/5 V, max load capacity 40 mA
Output 3…6 types:
- relay voltageless NOC contact, load capacity 2 A/230 VAC
Analog output types 1A and 2A:
–
analog voltage 0…10 V atR
load
1 k
–
analog current 0…20 mA, 4…20 mA at R
load
500