2.2. External Connection Diagrams
The separator has two terminal strip sockets, which two plugs with ter-
minal screws are connected to and enable the connection of external
wires with 2.5 mm
2
cross-section (terminals 6-9) and 1.5 mm
2
cross-
-section (terminals 1-5).
For the connection of signal terminals, one must use shielded wires.
The way to connect external signals is shown on the fig.2 on page 15.
The electrical connection diagram is also situated on the separator
casing.
3. SErVICE
After switching the separator on, the work state diode should light in red
for a moment, next it should light in green.
P20
supply
analog
output
Fig. 3. View of the P20G separator.
Diode of the separator work state:
- the state diode lights in green – normal
work,
- the state diode lights in red – improper work
parameters; one must configure the trans-
ducer again,
- the state diode pulsates in red – lack of
calibration or the non-volatile memory is
damaged; one must return the transducer to
the manufacturer.
Confirmation of the separator’s communication with PD14 programmer
is indicated by the status diode which turns off for short period of time.
To configure P20G separator is designed eCon software available on
the web site: www.lumel.com.pl.