64
40037
Sys Power
System Power (Read Only) is the Nominal system power based on the values
of Nominal system volts and Nominal system current.
40041
Word Order
Word Order controls the order in which Multifunction Meter receives or sends
floating - point numbers:- normal or reversed register order . In normal mode, the
two registers that make up a floating point numbers are sent most significant bytes
first. In reversed register mode , the two registers that make up a floating point
numbers are sent least significant bytes first. To set the mode, write the value ‘
2141.0’ into this register-the instrument will detect the order used to send this value
and set that order for all ModBus transaction involving floating point numbers.
40045
PT secondary
This address is used to read and write the PT secondary value.
Ref
TABLE 11
for the range of PT secondary settable values.
40043
CT secondary
This address is used to read and write the CT secondary value. Write one of the
following values to this address.
1:
1A CT secondary
5:
5A CT secondary
writing any other value will return an error.
This address is used to set Energy Digit Reset Count value. Energy count can be
configured to reset in between 7 to 9.
Energy Digit
Reset Count
40039
40047
Relay output
select
This address is used to select the Relay operation as pulse or Limit.
Write one of the following values to this address.
0:
Pulse output on Relay
128
(Decimal)
:
Limit output on Relay. Writing any other value will return an error.
40049
Pulse 1 / Limit 1
parameter
select
40051
Limit 1
Trip Point
40053
Limit 1
Hysteresis
This address is used to assign the Parameter to Relay
If Limit option is selected refer
TABLE 7
for parameter number & if Pulse option
is selected then refer
TABLE 9
.
This address is used to set the trip point in %. Any value between 10 to 100 for
Lo- alarm & 10 to120 (refer
TABLE 7
) for Hi-alarm can be written to this address.
Writing any other value will return an error.
This address is used to set the hysteresis between 0.5 to 50.0%. Writing any
other value will return an error.
40057
Limit 1 De-
energizing Delay
This address is used to set the Energizing delay between 1 to 10 . Writing any
other value will return an error.
This address is used to set the De-Energizing delay between 1 to 10 .
Writing any other value will return an error.
40055
Limit 1
Energizing Delay
EN