63
Address
Parameter
Description
40013
Pulse Width
of Relay
This address is used to set
pulse width
of the Pulse output.
Write one of the following values to this address:
60
:
60 ms
100
:
100 ms
200
:
200 ms
Writing any other value will return error .
40015
Reset Paramters This address is used to reset different parameters. Write specific value to this
register to reset the corresponding parameter. Writing any other value will return
an error.
Following are the values to reset various data.
0:
Energy Reset
1:
Demand Reset
2:
System Min Values Reset
3:
System Max Values Reset
4:
Run hour & On hour Reset
5:
No of Interruptions Reset
6:
Reset All data
40017
Number of Poles This address is used to set the no. of poles of generator of which RPM
is to be measured. The value must be between 2 to 40.
Writing any other value will return an error.
40019
Rs485 Set-up
Code
This address is used to set the baud rate, Parity, Number of stop bits. Refer to
TABLE 8
for details.
40021
Node Address
This register address is used to set Device address between 1 to 247 .
Explanation for 4 X register :
This address allows the user to set CT Primary value.
The settable range is 1 to 9999. It also depends on the per phase
1000 MVA Restriction of power combined with PT primary.
40035
CT Pimary
40033
PT Primary
This address allows the user to set PT Primary value (in terms of VL-L).
The settable range is 100 VL-L to 1200 kVL-L for all system types & also
depends on the per phase 1000 MVA Restriction of power combined with
CT primary.
40023
Pulse Divisor
This address is used to set
pulse divisor
of the Pulse output.
Write one of the following values to this address
for Wh
:
1
:
Divisor 1
10
:
Divisor 10
100
:
Divisor 100
1000
:
Divisor 1000
Writing any other value will return an error.
& In
kWh
or
MWh
divisor will be
1 default.