Result:
The Configure Equipment window opens.
............................................................................................................................................................
5
If the affected port is...
Then...
Looped back on itself
using patch cords at the
local DSX-3 panel or
equivalent connection
point,
Continue with
Connected to test
equipment,
Proceed to
In service,
Proceed to
............................................................................................................................................................
6
If the port is provisioned as Framed (M13) format, and it is looped
back on itself using patch cords at the local DSX-3 panel or
equivalent connection point, you have the following options to clear
the alarm.
1.
Remove the patch cords at the local DSX-3 panel or equivalent
connection point, or
2.
Ignore the alarm until the loopback is removed, (recommended
method), or
3.
Change the provisioning of the port that is looped back (continue
with
. ) This method is not recommended. The port must be
reprovisioned after the loopback is removed.
............................................................................................................................................................
7
In the Transmission section of the Configure Equipment window,
change the Signal Format parameter for the port to either C-Bit or
Clear Channel and click
Apply
.
Procedure 5-24: Clear
″
inc. DS3 Cbit
Mismatch
″
alarm
Trouble clearing procedures
....................................................................................................................................................................................................................................
5 - 7 2
Lucent Technologies
365-372-333 R2.1
Issue 4, June 2005