Lucent Technologies Lineage
®
2000 ECS-6U Controller J85501E-1
2 - 20 Product Description
Issue 4 August 1998
Table 2-B: Battery Plant Alarm Voltage Ranges
48-volt Plant
Range
Accuracy
High Voltage Shutdown
Thresholds (adjustable
in 0.5V increments)
49.0V to 60.0V
+/-0.5V
Equalize High Voltage
Shutdown Thresholds
(adjustable in 0.5V
increments)
51.0V to 60.0V
+/-0.5V
Battery on Discharge
Thresholds (adjustable
in 0.5V increments)
46.0V to 57.5V
+/-0.5V
24-volt Plant
Range
Accuracy
High Voltage Shutdown
Thresholds (adjustable
in 0.5V increments)
24.75V to 29.75V
+/-0.25V
Equalize High Voltage
Shutdown Thresholds
(adjustable in 0.5V
increments)
25.75V to 30.75V
+/-0.25V
Battery on Discharge
Thresholds (adjustable
in 0.5V increments)
23.0V to 28.50V
+/-0.25V
Table 2-C: ECS-6U Controller Physical Specifications
Dimensions
Width 21.5" (546 mm)
Depth 15.0" (381 mm)
Height 7.0" (178 mm)
Frame Mounting
Requirements
Standard 23" and 26" relay racks
Vertical mounting centers:
1.00" (25 mm)
Horizontal mounting centers:
22.32" (567 mm) for 23" rack-mount
24.32" (618 mm) for alternate 26"
rack-mount
Weight
14 pounds (6.4 kilograms)
Includes 113A2, EAT1, and BAD8