![Lucent Technologies J85501D-2 Product Manual Download Page 37](http://html.mh-extra.com/html/lucent-technologies/j85501d-2/j85501d-2_product-manual_1946208037.webp)
Lucent Technologies Lineage
®
2000 ECS-12 Controller J85501D-2
4 - 2 Installation and Setup
Issue 3 August 1998
to the controller. If the controller was damaged in transit, contact
the carrier for instructions for filing a damage claim. If the unit
must be returned to the factory due to damage, reuse the crate
and packing material.
Check the contents against the shipping bill for completeness.
•
Assembled ECS-12 Controller J85501D-2
•
Self-tapping mounting screws (#12-24 size)
•
Wire ties
•
Mounting brackets
•
ECS-12 Controller product manual, Select Code
167-790-033
•
ECS-12 Controller schematic and assembly drawings:
J85501D-2 and SD-82669-02
Default Factory
Settings
Factory settings for switches and jumpers for non-X controllers
should be set to the defaults shown in Table 4-A. However, all
switch and jumper settings should be verified as part of the
installation procedure.
Table 4-A: Default Factory Settings for Non-X Controllers
Jumper Settings
Board
Header
Jumper Pins
Function
Backplane
846575280
P602.1
2 and 3
-48 Volts
P602.2
P602.3
P602.4
CP1
P105
1 and 2
Restart enabled
P106
1 and 2
Equalize disabled
P108
1 and 2
For SR-series rectifiers
(Display)
P401
1 and 2
Shunt size less than
1000A
CP3
P302
1 and 2
-48 Volts
Switch Settings (0 = Open, 1 = Closed)
Board
Switch
Function
Switch Setting
-1 -2 -3 -4 -5 -6 -7 -8
CP1
SW101
HV/EQ Level
(-57 Volts)
1 1 0 0 1 0 N/A
SW102
HV/FL Level
(-55 Volts)
1 1 0 0 1 0 N/A
SW103
BD Level
(-53 Volts)
1 0 0 0 1 0 N/A
SW109
Meter Shunt
(300 Amps)
1 0 0 0 1 1 N/A
CP2
SW202
(See Table 4-B)
0 1 0 1 0 0 0 0