Lucent Technologies Lineage
®
2000 ECS-12 Controller J85501D-2
Issue 3 August 1998
Product Description 2 - 19
Altitude
-200 to13,000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet, derate maximum
temperature by 3.8 degrees Fahrenheit per 1000 feet above
5000 feet.
For altitudes of 1524 to 3962 meters, derate maximum
temperature by 0.656 degrees Celsius per 100 meters
above 1524 meters
Humidity
10% to 95% noncondensing
Electrostatic Discharge
IEC 801-2 Level 5 (15kV) at 40% relative humidity
Radiated & Conducted
Emissions
FCC Level A
Electromagnetic Immunity
10 V/m over the range of 20 to 2000 MHz
LVD/R Voltage Settings
40.5V +/-0.5V or 42.5V +/-0.5V
for 48V plants
20.25V +/-0.25V or 21.25V +/-0.25V for 24V plants
Table 2-B: Battery Plant Alarm Voltage Ranges
48 volt Plant
Range
Accuracy
High Voltage Shutdown
Thresholds
49.0V to 60.0V
+/-0.5V
Equalize High Voltage
Shutdown Thresholds
51.0V to 60.0V
+/-0.5V
Battery on Discharge
Thresholds
46.0V to 57.5V
+/-0.5V
24 Volt Plant
Range
Accuracy
High Voltage Shutdown
Thresholds
24.75V to 29.75V
+/-0.25V
Equalize High Voltage
Shutdown Thresholds
25.75V to 30.75V
+/-0.25V
Battery on
DischargeThresholds
23.0V to 28.50V
+/-0.25V
Table 2-A: ECS-12 Controller Electrical Specifications