Lucent Technologies 60V Small Broadband Power System J85500Q-1
2 - 8 Product Description
Issue 4 October 1998
Table 2-C: CPS 60-Volt/60 Hz Plant Specifications
60-volt/60 Hz dc Plant
One shelf with facilities to terminate up to
two 82-volt battery strings
Plant Architecture
Single shelf
AC Input Distribution
One ac feed per shelf
BPS Output Distribution
Four PWB mounted F-type connector for
each BPS output
Maximum Discharge Current
18 amperes per shelf
Maximum Recharge Current
Installed plant 82-volt rectifier capacity
minus plant 82-volt load.
Low Voltage Shut-off
64 ± 1 volt
or
61 ± 1 volt (strap selectable)
Operating Ambient Temperature
-40 to 149 degrees Fahrenheit
-40 to 65 degrees Celsius (Note 1)
Altitude
-200 to 13,000 feet
-61 to 3962 meters (Note 2)
Humidity
5 - 95% Non condensing
Audible Noise
<65 dBA measured 2 feet or 0.6 meters
from the plant.
Electrostatic Discharge
IEC 801-2 Level 4 (10KV) at 40% relative
humidity
Radiated and Conducted
Emissions
FCC Part 15, Level A
Electromagnetic Immunity
10 V/m over the range of 20MHz to 2000
MHz
Earthquake Rating
Zone 4, upper floors
Safety Agency Approvals
The CPS 60-volt/60 Hz shelf equipped
with the ES664 and ES635 is Underwriters
Laboratories (UL) Listed per Subject
Letter 1801: Power Distribution Center for
Communications Equipment. (Note 3)
Note 1: CPS can withstand temporary fluctuations in temperature up to 75°C
(167°F).
Note 2: For altitudes above 5000 feet, derate the temperature by 3.6 degrees Fahr-
enheit per 1000 feet. For altitudes above 1524 meters, derate the temperature by
0.656 degrees Celsius per 100 meters.
Note 3: Rectifier and BPS are individually UL Recognized to UL1950.