2000 ECS Battery Plant H569-403
5 - 2 Maintenance
Issue 4 February 1997
DC Circuit
Breakers/Fuses
Any circuit breaker mounted in the List 20 panel is ON (or
closed) when the handle is in the Up position, and OFF (or open)
in the Down position. A circuit breaker which is supplying a load
may be turned off manually, but this may affect service to the
load. All fuse blocks in the battery plant have indicating fuses
that allow a red element to pop out when a fuse blows (opens).
If a breaker has tripped off or a fuse blows, the overcurrent
problem should be cleared before restoring power to the load by
resetting the breaker or replacing the fuse. See
“Troubleshooting,” below, for information on tripped breakers
or blown fuses.
Troubleshooting
Table 5-A provides a list of observable trouble conditions, their
possible causes and the necessary corrective action for each
cause. The table is organized by the subsystem in which the
trouble is observed.