100 psi (690 kPa) Test Pressure (maximum)
Ambient Temperature During Cure Period
PIPE SIZE
60°F to 120°F
(16°C to 49°C)
40°F to 59°
(4°C to 15°C)
0°F to 39°F
(-18°C to 4°C)
¾" (20 mm)
15 mins.
15 mins.
30 mins.
1" (25 mm)
15 mins.
30 mins.
30 mins.
1¼" (32 mm)
15 mins.
30 mins.
2 hrs.
TABLE 3
Note 1:
For these sizes, the solvent cement can be applied at temperatures below 40°F (4.5°C),
however, the sprinkler system temperature must be raised to a temperature of 40°F (4.5°C) or
above and allowed to cure per the above recommendations prior to pressure testing.
Follow manufacturer’s instructions on pressure testing. Fill lines slowly and bleed
the air from the system prior to pressure testing.
Compatibility Notice
CPVC pipe can be damaged by contact with chemicals
contained in some construction products, such as:
‣
Edible oils
‣
Petroleum or solvent-based sealants
‣
Lubricants or firestop materials
‣
Glycol-based antifreeze
‣
Insulated wire
‣
See
FBCSystemCompatible.com
for complete list
7