Installation/Use/Maintenance Instructions
Fan coil units VFC, installation in sills
E
LTG Incorporated · PO Box 2889 · Spartanburg, S.C. 29304, USA
VFC_USA_BA (07/19)
Phone 864 599-6340, Fax -6344 · e-mail: [email protected] · Internet: www.LTG-INC.net
Former editions are invalid · Subject to technical modifications
page 6 of 19
4.
Technical specifications
4.1
Specification, dimensions, technical data VFC-0
4.1.1 2-pipe system (type VFC-0/2/…/T)
Specification
Fan coil unit with one heat exchanger for heating or cool
ing the ambient air.
Water-side control by valves.
Particularly small built-in depth and height, therefore
especially appropriate for a room-saving installation in
sills.
For extremely low inlet temperatures an insulated drain
pan is available.
Vertical installation.
Water connection on the right or left.
Dimensions, weights
Size
A
[inch]
B
[inch]
C
[inch]
D
[inch]
E
[inch]
Weight*
[lb]
500
20.7
19.5
22.1
28.7
27.3
28.6
630
24.7
23.5
26.1
34.8
31.3
33
800
33.7
32.5
35.1
42.7
40.3
42
1000
41.6
40.4
43
52.6
48.2
51
1250
49.5
48.3
50.9
61.1
56.1
62
* approx. values, depending on the exact model
Air outlet
6.5
2.2
0.7
3.6
4
5.1
Total length, dimension E
Dimension A
Dimension B
Unit length, dimension A
Length of condensate tray, dimension D
0.5
5.4
3
1.1
2.4
Suspension from above
(special version)
Standard:
bracket for
rear wall
installation
(accessory)
1.
9
6.
5
6.
1
4.
3
10.
5
16.
9
1.
1
2
.1
2.
1
1.
4
2.
1
2.
1
0.
87
Ø0
.6
Ø 0.33
17.
8
rubber stop
to be ordered
separately acc.
to wall clearance
Front view
Side view, right side
Auxiliary view A
Unit suspension, dimension C
2.1
61° angle of discharge
KW-RL
KW-VL
Mounting options:
- suspension from above (attachment to the sill)
- wall mounting - rear suspension
KW-VL = cold water inlet
KW-RL = cold water return