Chilled beams HDF-us-OM (01/17)
Phone 864 599-6340, Fax -6344 · [email protected] · www.LTG-INC.net
Former editions are invalid · Subject to technical modifications
page 9 of 30
Installation, operating and maintenance instructions
Active chilled beams HDF-600, ceiling installation
Continuation 4.2 Performance data
Size 2400, 2-way diffusion, 2-pipe system
V
P
cfm
Δ
p
in H
2
O
L
A18
dB(A)
L
wA
dB(A)
Q
P
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
1)
BTU/h
W
oc /
Δ
p
w
gpm / Ft H
2
O
81
0.28
15
21
87
209
5284
0.75 / 2
98
0.40
20
26
105
243
6232
118
0.60
25
31
125
264
6977
102
0.28
19
25
108
224
5967
123
0.40
23
29
131
251
6824
148
0.60
28
34
158
283
7891
127
0.28
23
29
135
228
6518
154
0.40
27
33
163
260
7592
184
0.60
32
38
196
302
8928
159
0.28
26
32
169
238
7286
192
0.40
31
37
205
272
8531
231
0.60
36
42
245
323
10,176
The chart shows examples for the unit design. A special
selection program is available for other flow rates, pri
mary pressures, temperatures and water flow rates.
Data refer to the unit including a secondary air grille
²
63 % free surface
Correction for other flow rates see section 4.3 (Caloric
output data).
1)
Water supply temperature: 61 °F
Air inlet temperature or return air temperature: 79 °F
2)
Water supply temperature: 104 °F
Air inlet temperature or return air temperature: 72 °F
Primary air temperature: 61 °F
V
P
- primary air flow rate (
±
3%)
p
- static pressure at the primary air connection
L
A18
- sound pressure level at 18 m
2
Sabine (
±
3 dB)
L
wA
- sound power level (
±
3 dB)
Q
P
- air-side cooling capacity (primary air
±
3 %)
Q
c
- water-side cooling capacity (secondary
±
6 %)
t
- temperature difference between air inlet and
water supply
w
oc
- standard water flow rate (cooling)
p
w
- water-side pressure loss
Summary of Contents for HDF-600
Page 31: ......