Building Safety. Building Security.

IS Thermal Detector AWEX-55000-440

The  addressable  Intrinsically  Safe  Thermal  Detector 

AWEX-55000-440  (fi g. B)  uses  the  heat  principle  and 

was  developed  for  the  fi re  detection  in  hazardous 

areas.  The  heat  detector  must  always  be  connected 

via a safety barrier, which has been approved for this 

detector, and a protocol interface. Furthermore, the re-

levant  country  specifi c  regulations  always  have  to  be 

observed.

The detector is assigned to Class A2S and can be used 

up to a room height of 6m. Depending on the parameter 

setup in the fi re detection control panel, the detector 

can operate either as maximum heat detector with an 

alarm temperature of 55°C, or as rate-of-rise heat de-

tector with a maximum temperature of 55°C.

The proven ADM loop technology with Apollo/Discovery 

protocol establishes a permanent communication bet-

ween the fi re detection control panel and the detector. 

That ensures a periodical function testing of the detec-

tor.  Fires  are  safely  detected  in  the  control  panel  by 

continuously analysing the measured values.

The two LEDs with 360° visibility indicate the activated 

condition of the detector. The detector address is se-

lected by means of a code card in the detector base. 

Therefore the detector can be changed without additi-

onal tools.

The detector is inserted into the IS Detector Base ASEX-

45681-215  (not  illustrated)  and  it  can  be  protected 

against theft.

Specifi cations

Ignition protection 

intrinsically safe

Ex classifi cation 

EEx ia IIC T5

Operating voltage 

Supply through loop voltage

Current consumption 

typ. 300µA (quiescent)

Ambient temperature 

 -20°C to +40°C (Class T5, no condensation or icing)

-20°C to +60°C (Class T4, no condensation or icing)

Relative humidity 

0 – 95% (no condensation)

Dimensions ø × H 

100 × 42 (mm)

Colour 

white

Weight 

100g

Approval 

EECS ATEX 0073

 

LPCB 010p

Order number 

242036

Order name 

IS Thermal Detector/Anal./XP95/Apo AWEX-55000-440

IS Detector Base ASEX-45681-215

The IS Detector Base ASEX-45681-215 is designed to 

accommodate intrinsically safe intelligent fi re detectors 

Series XP95 for use in ADM loops with Apollo/Discovery 

protocol.

Due to its robust multi-wire screw terminals, the detec-

tors can be wired with ease, thus achieving a secure 

and durable connection.

The detector address is selected by means of a code

card in the detector base. Therefore the detector can

be changed without additional tools.

The base is designed for surface mounting in hazardous 

areas. A mechanical theft protection of the detector can 

optionally be activated at the detector base.

Approval 

EECS ATEX 0073

 

LPCB 010q

Order number 

241024

Order name 

IS Optical Smoke Detector/Anal./XP95/Apo AOEX-55000-640